MT32 Prefabricated and modular wiring
Technical information
Approvals: System
Designed to comply with BS 7671 IEEWiring Regulations
Approvals: Connector
Designed to comply with EN 61535
(Fixed installation couplers for permanent connection)
Normal Voltage
230 volts
Frequency
50/60 Hertz
Volt Drop Line & Neutral Connector
1.0 mV/A/M
Volt Drop Line & Neutral
(Flexible Cabling System) 2.5mm
19.0 mV/A/M
Volt Drop Line & Neutral (Underfloor) 4.0mm
12.0 mV/A/M
Connector Impedance
1.0m Ω/connector
Connector, Body Material
PA66 – GF25
Connector Colour Female
Black
Connector Colour Male
White
Compatibility
Keyed against incorrect insertion
Operating Temperature (Ambient)
-5 ˚C to + 40 ˚C
Safety
PE contact engages first
Degree of Protection Engaged
IP2XC
Extension, Connection, Adaptor and Terminal Cables
Cable Type
3183B (HO5Z-F) to BS 6360 (LSOH)
Size
2.5mm
2
x 3 core
Connector Self Lock Retention
> 80N
Male/Female Connector Diameter
19.2 mm
Terminal Block
6 x 2.5mm
2
Adaptor (2.5mm
2
)
20mm
Extension, Connection, Adaptor and Terminal Cables
Cable Type
6491B (HO1Z-R) to BS 7211 (LSOH)
Size
4.0mm
2
x 3
Connector Self Lock Retention
> 80N
Male/Female Connector Diameter
19.2 mm
Terminal Block
6 x 4.0mm
2
Adaptor (4.0mm2)
20mm
General Specification
MT32Wiring distribution systems and accessories
Earthing requirements
for the installation of
equipment having High
Protective/Conductor
currents. BS 7671: 2008
Reg. 543.7
The scope of Reg. 543.7.1.3 requires
that every final circuit intended to
supply one or more items of
equipment, where the total protective
conductor current is likely to exceed
10mA. in normal use, shall have a high
integrity protective connection.
Flex System 2.5mm2 3 Core
Ring Final Circuit
MT32 ring flex system conforms to the
high integrity protective requirement
by having a ring protective conductor
of 2.5mm2 (543.7.2.1) providing the
ends of all protective conductors are
terminated independently at all
connection points throughout the
circuit. (543.7.1.4)
Singles Cabling
System 4.0mm²
Final Circuit
MT32 singles systems conform to the
high integrity protective requirement
by virtue of having a single copper
protective conductor of 4mm²,
(543.7.1.3ii) with the protective
conductor being enclosed throughout
in trunking or flexible conduit. provide
additional protection against
mechanical damage.
Different key ways apply between
2.5mm² and 4.0mm²
Note:
For technical information on
Home Run units and Lighting hubs
please call Technical hotline on
01424 856688