Background Image
Table of Contents Table of Contents
Previous Page  225 / 244 Next Page
Information
Show Menu
Previous Page 225 / 244 Next Page
Page Background

217

Irish

consumer units

protection devices and modular devices

Pack

Cat. Nos.

Insulated consumer units

IEC 60439 – IP30 – IK05 – Class 2

O

230 V 50Hz operating voltage

Surface mounting

Supplied completely assembled with neutral and

earth terminals

Insulated reversible back plate and door

Colour : white RAL 9010

Supplied complete with a set of pre-printed labels in

English and Irish for use with MCBs and RCDs

Supplied with blanking plates

Each consumer unit is fitted with :

• 63 A Neozed fuse unit complete with fuse

• 2 x 10 A type B MCBs

• 32 A type B MCB

• 63 A 30 mA RCD

• 4 x 20 A type B MCBs

Dimensions (mm)

Height x Width x Depth

1

6010 60

1 row unit

235 x 250 x 120

1

6010 61

2 row unit

360 x 250 x 120

1

6010 62

3 row unit

485 x 250 x 120

Accessories

White doors

1

0013 31

For 1 row unit

1

0013 32

For 2 row unit

Transparent doors

1

0013 41

For 1 row unit

1

0013 42

For 2 row unit

Joining accessories

Consisting of spacers and an arched cable gland for

joining 2 units together

1

0013 92

Vertical (across whole width)

6010 60

0013 42

0013 31

6010 61

1 : Min. protection for Icc max : 10 kA

Please note :

The products shown on this page

represent the most commonly used items in the range.

Additional versions, including surface and flush

boards, are also available on request.

RX

3

residential MCBs - 6 kA

Short circuit capacity : 6 000 A (IS EN 60898-1)

Type B – 6 kA

Single pole

(1 protected pole)

230/400 V

±

B curve

Nominal rating

Number of

(In)

17·5 mm modules

10

4022 71

10 A

1

10

4022 73

20 A

1

10

4022 75

32 A

1

10

4022 76

40 A

1

Specials available on request

Pack

Cat. Nos.

Residual current devices (RCDs)

Type AC

Conform to IS EN 61008-1

Double pole 230 V

±

Type AC

Nominal rating

Number of

(In)

17·5 mm modules

30 mA sensitivity

1

0086 29

40 A

2

1

0086 30

63 A

2

DX RCBOs - 10 kA

Conform to BS EN 61009-1

Breaking capacity : 10 kA to BS EN 61009-1

Type B MCB and 30 mA RCD protection

B curve

Nominal rating

Number of

(In)

17·5 mm modules

1

0077 78

10 A

2

1

0077 80

16 A

2

1

0077 81

20 A

2

1

0077 83

32 A

2

1

0077 84

40 A

2

Bells and buzzer

50 Hz AC

Connection by screw terminals, with label holder

Bells

- IP 30-1

Number

Voltage

Power

Consum.

P

1

of 17·5 mm

(V

±

)

(VA)

(mA)

(dB)

modules

10

0041 01 8/12

4/5

360/420

80/84

1

10

0041 07 230

6

27

83

1

Buzzer

- IP 30-1

10

0041 13 230

6

27

73

1

0086 30

0041 07

0041 13

Spare terminals available

(see current Industrial

and power protection catalogue)

Modular timers

(p. 26)

Voltage surge protector

For neutral earthing : TT, TN, IT, U

c

= 440 V

Type 1 : I

imp

= 10 kA (impulse discharge cap.

10/350 µs wave)

Type 2 : I

n

= 20 kA; Up = 2 kV (protection level)

I

max

= 70 kA (impulse discharge cap. 8/20 µs)

Number

of 17·5mm

Associated protection modules

1

0039 20 Single pole

0068 64

1

Voltage surge protection technical information p. 221

Bell transformers

d

Conform to IEC/EN 61558-2-8

Supplied with label holder

Protected against overloads and short circuits

Power to 8 V-12 V or 24 V access control devices

such as bells and chimes

Possibility for supply busbars to run through

(Cat. Nos. 4130 90/91)

Number

Secondary (V)

Rating (A)

Power (VA)

of 17·5 mm

modules

230 V / 8 V

1

4130 90 8 V

±

0·5 A

4 VA

2

230 V / 12 V - 8 V

1

4130 91 12/8 V

±

0·66/1 A

8 VA

2

230 V / 24 V - 12 V

1

4130 93 24/12 V

±

1/1·5 A

24/18 VA

4

NEW