Background Image
Table of Contents Table of Contents
Previous Page  84-85 / 319 Next Page
Information
Show Menu
Previous Page 84-85 / 319 Next Page
Page Background

klik.system | Specification guide to prefabricated wiring systems

22

Connection to the fixed wiring

BS 7671 specifies the products that may be used to facilitate

connection to each fixed lighting point. A plug-in lighting

distribution unit to BS 5733 is identified as an appropriate

product, particularly in suspended ceilings, where one plug-in

lighting distribution unit may be used for a number of

luminaires.

Where a wiring system comprising of a single circuit

terminates at an assembly containing couplers intended for

branching of a circuit, the assembly is required by BS 8488 to

comply with specific standards depending on the

assembly designation. Where the assembly containing

couplers is specifically designated for the connection of

luminaires, it is classified as a lighting distribution unit and

must comply with BS 5733 (see figure 10).

Lighting Distribution Unit