Background Image
Table of Contents Table of Contents
Previous Page  270-271 / 319 Next Page
Information
Show Menu
Previous Page 270-271 / 319 Next Page
Page Background

11

The Wiring Rules & Building regulations are not the only documents

that need to be consulted, another important document relates to

smoke alarms.

BS 5839-6:2004 Fire detection and Fire

alarm systems for buildings

This Code of Practice has particular requirements for dwellings.

This document makes reference to the power supply to such systems

and mentions RCD’s. The circuit supplying these systems should

preferably not be protected by an RCD. This however is going to be

difficult to achieve if the circuit supplying these systems is buried in

the walls and standard domestic wiring systems are used. Indeed the

supply cables would need to be specially protected in earthed metal

conduit etc. for RCD protection not to be used.

Options for circuits supplying fire or smoke alarms in dwellings

protected by an RCD include:

i. The RCD serves only that circuit. For example with the use of an

RCBO

ii. The RCD operates independently of any RCD feeding socket

outlets or portable equipment

So consideration of these points is necessary during the design stage

and particular care is needed to select the appropriate consumer unit

and wiring system to ensure compliance. BS 5839-6 should always

be studied to ensure that all relevant recommendations are complied

with.

Where RCD protection is needed for smoke detector

circuits one option is to supply that circuit only

The following options, each with their own benefits, can be

considered by the installation designer.