4.53

Sales Service Centre • 01952 675612   Technical Support Helpline • 01952 675689

MCCBs, Moulded Case Switches

x250

MCCBs

Magnetic and thermal settings

220/240V AC

IEC 60 947-2

380/415V AC

IEC 60 947-2

HHB

Icu 35 kA

25 kA

Ics 25 kA

20 kA

HNB

Icu 85 kA

40 kA

Ics 40 kA

20 kA

HCB

Icm -

9 kA

Icw -

3 kA - 1s

Ech. 50%

Ech. 25%

PUSHTOTRIP

PUSHTOTRIP

PUSHTOTRIP

Thermal adjustment from 0.63 to 1 x In

Magnetic adjustment from 6 to 13 x In (100 - 200A)

from 5 to 11 x In (250A)

Ech. 50%

PUSHTOTRIP

6

TRIP

100 - 200A

250A

Ir (x In)

0.63 - 0.8 - 1 x In

Ii (x In)

6 - 8 - 10 - 13 x In 5 - 7 - 9 - 11 x In

x In/Ii

0 - 100%

0 - 60%

Ech. 80 %

5

8

10

13

l i (xIn)

6

l r (xIn)

0.63

0.8

1

PUSHTOTRIP

6

5

8

10

13

%0

100%

l i (xIn)

xIn / Ii

l r (xIn)

0.63

0.8

1

6

Protection