1.105
Data is subject to errors and technical modifications.
MCCBs x160
Technical Data
Commercial
Distribution
Tripping curve
MCCB x160
MCCB Disconnection Data
Thermal constraint curve at 400V (Let-through energy)
MCCB x160
Current limiting curve at 400V (Let-through peak current)
MCCB x160
16A
40A
63A
80A
100A
125A
160A
I
2
t (A s)
2
10
4
10
5
10
6
10
7
10
1
10
2
1
0.1
IPF (kA rms)
125A
0.8
0.5
0.3
0.25
0.7
0.9
16A
40A
63A
80A 100A
160A
0.1
1
10
100
10
10
1
0.1
IPF (kA rms)
Ip (kA)
1
2
0.01
0.1
1
10
100
1000
10000
1
10
100
Tripping time (sec)
x In @ Tcal (A)
160A
80A
100A, 40A
63A
32A
25A
20A
16A
125A, 50A
The magnetic
threshold trippting
curves is mean value.
The tripping area is
Irm ±20%
Earth Fault Loop Impedance Data
Disconnection time 0.2s, 0.4s, 1s
Device
rating
(A)
Instantaneous
trip (xI n )
Instantaneous
trip (A)
add 20% tole-
rance (I a )
Zs = (230 x
0.95) / I a
16
40.3
644.8
773.8
0.28
20
32.2
644.0
773
0.28
25
25.7
643
771
0.28
32
20.13
644.2
773.0
0.28
40
15.0
600.0
720.0
0.30
50
12.0
600.0
720.0
0.30
63
16.6
1045.8
1255.0
0.17
80
13.1
1048.0
1258
0.17
100
15.4
1540.0
1848.0
0.12
126
12.3
1538
1845.0
0.12
160
10.22
1635.2
1962.2
0.11
Disconnection time 5s
Device
rating
(A)
trip (xI n )
I a (A)
Zs = (230 x 0.95)
/ I a
16
10
160
1.37
20
10
200
1.09
25
10
250
0.87
32
10
320
0.68
40
10
400
0.55
50
10
500
0.44
63
10
630
0.35
80
10
800
0.27
100
10
1000
0.22
125
10
1250
0.17
160
10
1600
0.14
The earth fault loop impedance requirements for larger devices can be calcula-
ted by the formula given in BS7671:2008
Zs ≤ 230 x Cmin
l a
Where l a = I n of MCCB x Mag setting x 1.2