1.105

Data is subject to errors and technical modifications.

MCCBs x160

Technical Data

Commercial

Distribution

Tripping curve

MCCB x160

MCCB Disconnection Data

Thermal constraint curve at 400V (Let-through energy)

MCCB x160

Current limiting curve at 400V (Let-through peak current)

MCCB x160

16A

40A

63A

80A

100A

125A

160A

I

2

t (A s)

2

10

4

10

5

10

6

10

7

10

1

10

2

1

0.1

IPF (kA rms)

125A

0.8

0.5

0.3

0.25

0.7

0.9

16A

40A

63A

80A 100A

160A

0.1

1

10

100

10

10

1

0.1

IPF (kA rms)

Ip (kA)

1

2

0.01

0.1

1

10

100

1000

10000

1

10

100

Tripping time (sec)

x In @ Tcal (A)

160A

80A

100A, 40A

63A

32A

25A

20A

16A

125A, 50A

The magnetic

threshold trippting

curves is mean value.

The tripping area is

Irm ±20%

Earth Fault Loop Impedance Data

Disconnection time 0.2s, 0.4s, 1s

Device

rating

(A)

Instantaneous

trip (xI n )

Instantaneous

trip (A)

add 20% tole-

rance (I a )

Zs = (230 x

0.95) / I a

16

40.3

644.8

773.8

0.28

20

32.2

644.0

773

0.28

25

25.7

643

771

0.28

32

20.13

644.2

773.0

0.28

40

15.0

600.0

720.0

0.30

50

12.0

600.0

720.0

0.30

63

16.6

1045.8

1255.0

0.17

80

13.1

1048.0

1258

0.17

100

15.4

1540.0

1848.0

0.12

126

12.3

1538

1845.0

0.12

160

10.22

1635.2

1962.2

0.11

Disconnection time 5s

Device

rating

(A)

trip (xI n )

I a (A)

Zs = (230 x 0.95)

/ I a

16

10

160

1.37

20

10

200

1.09

25

10

250

0.87

32

10

320

0.68

40

10

400

0.55

50

10

500

0.44

63

10

630

0.35

80

10

800

0.27

100

10

1000

0.22

125

10

1250

0.17

160

10

1600

0.14

The earth fault loop impedance requirements for larger devices can be calcula-

ted by the formula given in BS7671:2008

Zs ≤ 230 x Cmin

l a

Where l a = I n of MCCB x Mag setting x 1.2