BETA Protecting

Low-Voltage Fuse Systems

3

NH LV HRC fuse bases

3/50

Siemens ET B1 · 10/2008

3

*

You can order this quantity or a multiple thereof.

Benefits

Technical specifications

The silver-plated Lyra contact provides a large contact area

for the contact blade of the LV HRC fuse link. This improves

heat transmission and lowers the temperature. It also mini-

mizes aging of the fuse link in the maximum load range, in

particular when using SITOR fuses

The large contact area also facilitates replacement of

LV HRC fuse links

The spring washer that tensions the contact is mechanically

galvanized. This prevents hydrogen embrittlement. The con-

tact is resistant to aging and there will be no dreaded

annealing of contacts, which considerably improves operating

safety.

LV HRC fuse bases, LV HRC bus-mounting bases

Size

000/00

0

1

2

3

4

Standards

IEC 60269-1, -2; EN 60269-1; DIN VDE 0636-2

Rated current

I

n

A

160

160

250

400

630

1250

Rated voltage U

n

V AC 690

690

(

Also suitable for 1000 V SITOR fuse links)

V DC 250

440

Rated breaking capacity

kA AC 120

kA DC 25

Flat terminals

Screw

M8

M10

M12

Nut

M8

--

Max. tightening torque

Nm 14

38

65

Plug-in terminals

Conductor cross-section

mm

2

2.5 ... 50

--

Saddle-type terminals

Conductor cross-section

mm

2

6 ... 70

--

Box terminals

Conductor cross-section

mm

2

2.5 ... 50

Terminal strips

Conductor cross-section, 3-wire

mm

2

1.5 ... 16

--

Max. torque

for attachment of LV HRC fuse base

Nm 2

2.5

--

LV HRC fuse bases with slewing equipment

LV HRC fuse bases with swivel mechanism

Size

000/00

1

3

4

a

Rated voltage U

n

V AC 690

V DC 440

Power loss

W 4

5

20

32

Flat terminals

Screw

M8

M10

M12

M16

Nut

M8

--

Max. tightening torque

Nm 14

38

65

© Siemens AG 2008