ALPHA FIX Terminal Blocks
Terminals with Spring-Loaded Connection
8WH through-type terminals
12/10
Siemens ET A1 · 10/2008
12
8WH2 000-0CG07 8WH2 003-0CG07 8WH2 004-0CG07 8WH2 000-0AH00
8WH2 000-0AH01
8WH2 003-0AH00
8WH2 003-0AH01
Dimensions
• Width / length / width of cover in mm
6.2 / 56 / 2.2
6.2 / 71.5 / 2.2
6.2 / 87 / 2.2
8.2 / 69.5 / 2.2
8.2 / 90.5 / 2.2
• Height (NS 35/7.5 / NS 35/15) in mm
36.8 / 44
36.5 / 44
43.5 / 51
Technical specifications acc. to IEC/DIN VDE
• Max. load current in A / cross-section in mm²
--
52 / 10
• Rated impulse withstand voltage in kV / pollution de-
gree
8 / 3
• Overvoltage category / insulating group
III / I
Connection capacities
• Flexible with end sleeve with plastic sleeve in mm² 0.25 ... 4
0.25 ... 6
• Flexible with end sleeve without plastic sleeve in
mm²
0.25 ... 4
0.25 ... 6
• Flexible with two-wire connection end sleeve with
plastic sleeve in mm²
0.5 ... 1
0.5 ... 1.5
Stripped length in mm
10
12
Plug gage (IEC 60947-1)
A4
A5
Insulation type
PA
• Flammability class acc. to UL 94
V0
Approval data (UL/CUL and CSA)
• Rated voltage / current / cable sizes
- UL/CUL: in V/A / AWG
-- / -- / 20-10
600 / 50 / 20-8
- CSA: in V/A / AWG
--
Support rails/protective conductor busbars
See section
Support rails
See section
Support rails
See section
Support rails
--
--
8WH2 000-0CH07
8WH2 003-0CH07
8WH2 000-0AJ00
8WH2 000-0AJ01
8WH2 000-0CJ07
Dimensions
• Width / length / width of cover in mm
8.2 / 69.5 / 2.2
8.2 / 90.5 / 2.2
10 / 71.5 / 2.2
• Height (NS 35/7.5 / NS 35/15) in mm
43.5 / 51
50.5 / 58
Technical specifications acc. to IEC/DIN VDE
• Max. load current in A / cross-section in mm²
--
65 / 16
• Rated impulse withstand voltage in kV / pollution de-
gree
8 / 3
• Overvoltage category / insulating group
III / I
Connection capacities
• Flexible with end sleeve with plastic sleeve in mm² 0.25 ... 6
0.25 ... 10
• Flexible with end sleeve without plastic sleeve in
mm²
0.25 ... 6
0.25 ... 10
• Flexible with two-wire connection end sleeve with
plastic sleeve in mm²
0.5 ... 1.5
1.5 ... 2.5
Stripped length in mm
12
18
Plug gage (IEC 60947-1)
A5
A6
Insulation type
PA
• Flammability class acc. to UL 94
V0
Approval data (UL/CUL and CSA)
• Rated voltage / current / cable sizes
- UL/CUL: in V/A / AWG
-- / -- / 20-8
600 / 65 / 16-6
-- / -- / 16-6
- CSA: in V/A / AWG
--
Support rails/protective conductor busbars
See section Support rails See section Support rails --
See section Support rails
© Siemens AG 2008