17/166 Circuit-breakers, switch-disconnectors

2010 CA08103002Z-EN

www.eaton.com

Max. rated uninterrupted current 160 A

NZMB1

NZMC1

NZMN1

NZMH1

Switching capacity

Rated short-circuit making capacity

240 V

I

cm

kA

63

121

187

220

400/415 V

I

cm

kA

53

76

105

220

440 V

I

cm

kA

53

63

74

74

525 V

I

cm

kA

24

40

40

690 V

I

cm

kA

14

17

17

Rated short-circuit breaking capacity I

cn

I

cu

according to IEC/EN 60947

Operating sequence O-t-CO

240 V 50/60 Hz

I

cu

kA

30

55

85

100

400/415 V 50/60 Hz

I

cu

kA

25

36

50

100

440 V 50/60 Hz

I

cu

kA

25

30

35

70

525 V 50/60 Hz

I

cu

kA

12

20

20

690 V 50/60 Hz

I

cu

kA

8

10

10

500 V DC

3)

I

cu

kA

15

30

750 V DC

3)

I

cu

kA

I

cs

according to IEC/EN 60947

Operating sequence O-t-CO-t-CO

240 V 50/60 Hz

I

cs

kA

30

55

85

100

400/415 V 50/60 Hz

I

cs

kA

25

36

50

50

440 V 50/60 Hz

I

cs

kA

18.5

22.5

35

35

525 V 50/60 Hz

I

cs

kA

6

10

10

690 V 50/60 Hz

I

cs

kA

4

7.5

7.5

Maximum LV h.b.c. fuse

6)

A gG/gL NZM.1-…20…100: 200

NZM.1-…125, 160: 315

Rated short-time withstand current

t = 0.3 s

I

cw

kA

t = 1 s

I

cw

kA

Utilization category according to IEC/EN 60947-2

A

A

A

A

Rated making and breaking capacity

Rated operational

current

AC-1

400/415 V 50/60 Hz

I

e

A

160

160

160

160

690 V 50/60 Hz

I

e

A

160

160

160

160

AC-3

400/415 V 50/60 Hz

I

e

A

160

160

160

160

690 V 50/60 Hz

I

e

A

160

160

160

160

DC-1

3)

500 V DC

I

e

A

125

125

750 V DC

I

e

A

DC-3

3)

500 V DC

I

e

A

125

125

750 V DC

I

e

A

Lifespan, mechanical

of which max. 50 % trip by shunt/undervoltage release

Operations

20000

20000

20000

20000

Lifespan, electrical

AC-1

400/415 V 50/60 Hz

Operations

7500

7500

10000

10000

690 V 50/60 Hz

Operations

5000

7500

7500

AC-3

400/415 V 50/60 Hz

Operations

7500

7500

690 V 50/60 Hz

Operations

5000

5000

DC-1

3)

500 V DC

Operations

10000

10000

750 V DC

Operations

DC-3

3)

500 V DC

Operations

5000

5000

750 V DC

Operations

Max. operating frequency

Ops/h 120

120

120

120

Heat dissipation per pole at I

u 5)

W 16.7

16.7

16.7

16.7

Total opening delay on short-circuit

ms

< 10

< 10

< 10

< 10

Technical data that diverge from products for the IEC market

Switching capacity of NA switch (UL489, CSA 22.2 No. 5-09)

Short-circuit current rating (SCCR)

240 V 60 Hz

kA

35

85

480 V 60 Hz

kA

25

1)

35

1)

600 V 60 Hz

kA

Notes

1)

Switching capacity of NA switches with NZM…1‐…(C)NA: 480 Y/277 V

2)

For rated operational current AC-3 with NZM4: 400 V: max. 650 kW; 690 V: max. 600 kW

3)

DC data apply only for NZM...A... with thermomagnetic release