Full-load motor-running currents in amperes

corresponding to various AC horsepower ratings

2010

CA08103002Z-EN

www.eaton.com

HP

110 - 120

V

220 - 240

V

a,b

360 - 380

V

440 - 480

V

550 - 600

V

Single

phase

Two

phase

Three

phase

Single

phase

Two

phase

Three

phase

Single

phase

Three

phase

Single

phase

Two

phase

Three

phase

Single

phase

Two

phase

Three

phase

1/10

3.0

–

–

1.5

–

–

1.0

–

–

–

–

–

–

–

1/8

3.8

–

–

1.9

–

–

1.2

–

–

–

–

–

–

–

1/6

4.4

–

–

2.2

–

–

1.4

–

–

–

–

–

–

–

1/4

5.8

–

–

2.9

–

–

1.8

–

–

–

–

–

–

–

1/3

7.2

–

–

3.6

–

–

2.3

–

–

–

–

–

–

–

1/2

9.8

4.0

4.4

4.9

2.0

2.2

3.2

1.3

2.5

1.0

1.1

2.0

0.8

0.9

3/4

13.8

4.8

6.4

6.9

2.4

3.2

4.5

1.8

3.5

1.2

1.6

2.8

1.0

1.3

1

16.0

6.4

8.4

8.0

3.2

4.2

5.1

2.3

4.0

1.6

2.1

3.2

1.3

1.7

1-1/2

20.0

9.0

12.0

10.0

4.5

6.0

6.4

3.3

5.0

2.3

3.0

4.0

1.8

2.4

2

24.0

11.8

13.6

12.0

5.9

6.8

7.7

4.3

6.0

3.0

3.4

4.8

2.4

2.7

3

34.0

16.6

19.2

17.0

8.3

9.6

10.9

6.1

8.5

4.2

4.8

6.8

3.3

3.9

5

56.0

26.4

30.4

28.0

13.2

15.2

17.9

9.7

14.0

6.6

7.6

11.2

5.3

6.1

7-1/2

80.0

38.0

44.0

40.0

19.0

22.0

27.0

14.0

21.0

9.0

11.0

16.0

8.0

9.0

10

100

48.0

56.0

50.0

24.0

28.0

33.0

18.0

26.0

12.0

14.0

20.0

10.0

11.0

15

135

72.0

84.0

68.0

36.0

42.0

44.0

27.0

34.0

18.0

21.0

27.0

14.0

17.0

20

–

94.0

108

88.0

47.0

54.0

56.0

34.0

44.0

23.0

27.0

35.0

19.0

22.0

25

–

118

136

110

59.0

68.0

70.0

44.0

55.0

29.0

34.0

44.0

24.0

27.0

30

–

138

160

136

69.0

80.0

87.0

51.0

68.0

35.0

40.0

54.0

28.0

32.0

40

–

180

208

176

90.0

104

112

66.0

88.0

45.0

52.0

70.0

36.0

41.0

50

–

226

260

216

113

130

139

83.0

108

56.0

65.0

86.0

45.0

52.0

60

–

–

–

–

133

154

–

103

–

67.0

77.0

–

53.0

62.0

75

–

–

–

–

166

192

–

128

–

83.0

96.0

–

66.0

77.0

100

–

–

–

–

218

248

–

165

–

109

124

–

87.0

99.0

125

–

–

–

–

–

312

–

208

–

135

156

–

108

125

150

–

–

–

–

–

360

–

240

–

156

180

–

125

144

200

–

–

–

–

–

480

–

320

–

208

240

–

167

192

250

–

–

–

–

–

602

–

403

–

–

302

–

–

242

300

–

–

–

–

–

–

–

482

–

–

361

–

–

289

350

–

–

–

–

–

–

–

560

–

–

414

–

–

336

400

–

–

–

–

–

–

–

636

–

–

477

–

–

382

500

–

–

–

–

–

–

–

786

–

–

590

–

–

472

a)

To obtain full-load currents for 200 and 208 V motors, increase corresponding 220 - 240 V ratings by 15 and 10 percent, respectively.

b)

To obtain full-load currents for 265 and 277 V motors, decrease corresponding 220 - 240 V ratings by 13 and 17 percent, respectively.

Quote from “Power Conversion Equipment - UL 508C, May 3, 2002”.

Reproduced from UL 508 C, Power Conversion Equipment, 3rd edition (May 2, 2002) with permission of Underwriters Laboratories Inc.