Background Image
Table of Contents Table of Contents
Previous Page  51 / 51
Information
Show Menu
Previous Page 51 / 51
Page Background

22/38

Full-load motor-running currents in amperes

corresponding to various AC horsepower ratings

2010

CA08103002Z-EN

www.eaton.com

HP

110 - 120

V

220 - 240

V

a,b

360 - 380

V

440 - 480

V

550 - 600

V

Single

phase

Two

phase

Three

phase

Single

phase

Two

phase

Three

phase

Single

phase

Three

phase

Single

phase

Two

phase

Three

phase

Single

phase

Two

phase

Three

phase

1/10

3.0

1.5

1.0

1/8

3.8

1.9

1.2

1/6

4.4

2.2

1.4

1/4

5.8

2.9

1.8

1/3

7.2

3.6

2.3

1/2

9.8

4.0

4.4

4.9

2.0

2.2

3.2

1.3

2.5

1.0

1.1

2.0

0.8

0.9

3/4

13.8

4.8

6.4

6.9

2.4

3.2

4.5

1.8

3.5

1.2

1.6

2.8

1.0

1.3

1

16.0

6.4

8.4

8.0

3.2

4.2

5.1

2.3

4.0

1.6

2.1

3.2

1.3

1.7

1-1/2

20.0

9.0

12.0

10.0

4.5

6.0

6.4

3.3

5.0

2.3

3.0

4.0

1.8

2.4

2

24.0

11.8

13.6

12.0

5.9

6.8

7.7

4.3

6.0

3.0

3.4

4.8

2.4

2.7

3

34.0

16.6

19.2

17.0

8.3

9.6

10.9

6.1

8.5

4.2

4.8

6.8

3.3

3.9

5

56.0

26.4

30.4

28.0

13.2

15.2

17.9

9.7

14.0

6.6

7.6

11.2

5.3

6.1

7-1/2

80.0

38.0

44.0

40.0

19.0

22.0

27.0

14.0

21.0

9.0

11.0

16.0

8.0

9.0

10

100

48.0

56.0

50.0

24.0

28.0

33.0

18.0

26.0

12.0

14.0

20.0

10.0

11.0

15

135

72.0

84.0

68.0

36.0

42.0

44.0

27.0

34.0

18.0

21.0

27.0

14.0

17.0

20

94.0

108

88.0

47.0

54.0

56.0

34.0

44.0

23.0

27.0

35.0

19.0

22.0

25

118

136

110

59.0

68.0

70.0

44.0

55.0

29.0

34.0

44.0

24.0

27.0

30

138

160

136

69.0

80.0

87.0

51.0

68.0

35.0

40.0

54.0

28.0

32.0

40

180

208

176

90.0

104

112

66.0

88.0

45.0

52.0

70.0

36.0

41.0

50

226

260

216

113

130

139

83.0

108

56.0

65.0

86.0

45.0

52.0

60

133

154

103

67.0

77.0

53.0

62.0

75

166

192

128

83.0

96.0

66.0

77.0

100

218

248

165

109

124

87.0

99.0

125

312

208

135

156

108

125

150

360

240

156

180

125

144

200

480

320

208

240

167

192

250

602

403

302

242

300

482

361

289

350

560

414

336

400

636

477

382

500

786

590

472

a)

To obtain full-load currents for 200 and 208 V motors, increase corresponding 220 - 240 V ratings by 15 and 10 percent, respectively.

b)

To obtain full-load currents for 265 and 277 V motors, decrease corresponding 220 - 240 V ratings by 13 and 17 percent, respectively.

Quote from “Power Conversion Equipment - UL 508C, May 3, 2002”.

Reproduced from UL 508 C, Power Conversion Equipment, 3rd edition (May 2, 2002) with permission of Underwriters Laboratories Inc.