Background Image
Table of Contents Table of Contents
Previous Page  142 / 164 Next Page
Information
Show Menu
Previous Page 142 / 164 Next Page
Page Background

142

WIRING ACCESSORIES AND SINGLE PHASE DISTRIBUTION

PG00400018U – March 2012

RCBOs technical data

Specifications

Product standard

IEC/EN 61009

No of poles

1P & solid N

Mechanical specification

Device width

17.7 mm

Terminal type

Box clamp

Mounting

DIN rail

Degree of protection

IP 20

Positive contact indication

Yes (red/green)

Electrical specification

Rated voltage

230/240 V AC

Current ratings

6, 10, 16, 20, 25, 32, 40, 45A

Rated impulse

and withstand voltage

4kV (1.2/50 µ sec)

Rated short circuit capacity

6kA

Sensitivity

AC

Tripping characteristic

Instantaneous Tripping current I mt Type B: 3 In < Imt < 5 In

Type C: 5 In < Imt < 10 In

Conventional non tripping current I nt 1.13 In

Conventional tripping current It

1.45 In

Ref / Calibration temp

40

o

C

Rated residual tripping current

30mA

Residual tripping type

Instantaneous

Number of operating cycles elec

>4000

Number of operating cycles mech

>20000

RCBOs dimensions (mm)

Compact Residual Current Circuit Breakers – with Overload protection (RCBOs) technical data

Eaton’s range of new compact Residual Current Circuit Breakers with integral Overload protection (RCBOs), are manufactured to IEC/EN

61009 and meet the latest European and International standards.

DIN rail mountable in a single module width these RCBOs provide a comprehensive protection solution to a wide range of applications.

With standard current ratings from 6A to 45A, in both B and C Type characteristics and a trip sensitivity of 30mA, these devices are the

ideal choice for domestic applications.

The Eaton RCBOs suite with the complete range of modular devices, and are for use within Eaton’s MEM Memera consumer units and

other applications.

These devices will accommodate cables up to 16mm

2

.

Trip Sensitivity

30mA Standard

Provides a high degree of protection against electric shock due to direct and indirect contact. A 30mA RCD will trip within 40mS when a

fault current of 150mA is detected.

This type of RCD is required to satisfy the requirements for “Additional Protection” in accordance with BS7671

(IEE wiring regs.) Other sensitivities are available on request.

Technical data

Switch and protection devices dimensions and data

12.5

LOAD

LINE

Terminal capacity

1–16mm

2

1–25mm

2

Terminal screw

M4

M5

Terminal torque recommended

1.2–1.5Nm

2.0–2.5Nm