Background Image
Table of Contents Table of Contents
Previous Page  135 / 164 Next Page
Information
Show Menu
Previous Page 135 / 164 Next Page
Page Background

WIRING ACCESSORIES AND SINGLE PHASE DISTRIBUTION

PG00400018U – March 2012

135

Technical data

Consumer units and enclosures dimensions and data

12.4

Enclosures, dimensional drawings IP65

Eaton list

No of

number

Finish

modules

A

B

C

D

E

BC-MP65-1/3

Moulded

1–3

150 100 100 84

50

BC-MP65-1/5

Moulded

1–5

200 126 125 120 50

BC-MP65-1/9

Moulded

1–9

200 200 125 120 120

A

B

E

C

D

Enclosure type BC-MP65

Enclosure type AN

Eaton list

Number

number

Finish

of modules

A

B

C

AN2

Moulded

2

135

40

65

AN2D

1)

Moulded

2

135

40

65

AN25

Moulded

2

135

50

65

AN2EBD

1), 2)

Moulded

2

135

40

65

AN4EBLS

2)

Moulded

4

135

110

88

1)

Isolator fitted.

2)

Sealable supply terminal access, independent access to load terminals.

Consumer units and enclosures technical data

Earth

Neutral

Isolator

RCCB

RCBO

MCB

Connection type

Pinch screw

Pinch screw

Box clamp

Box clamp

Box clamp

Box clamp

Screw type

Combination

Combination

Combination

Combination

Combination

Combination

Size

M5

M5

M6

M5

M5

M5

Min cable size

1mm

2

1mm

2

2.5mm

2

1mm

2

1mm

2

1mm

2

Max cable size

16mm

2

16mm

2

50mm

2

35mm

2

25mm

2

/16mm

2

25mm

2

Recommended torque

Note 1

Note 1

2.5Nm

2.0Nm

2.0Nm

2.0Nm

Maximum torque

Note 1

Note 1

5.0Nm

2.4Nm

2.4Nm

2.4Nm

Note: As terminal is pinch screw, the torque will depend upon cable size and type and should be sufficient to secure termination without damaging conductor strands.

A

B

C

A

B

C

Enclosures dimensions IP40