J FRAME MCCBs
I
Current
Minimum 1 Pole
3
Pole
3
P SwN
Rating (A)
Setting (A)
LIST No
LIST No
LIST No
16
13
7
PBJN116 7PBJN316 N/A
20
16
7
PBJN120 7PBJN320 N/A
25
17.5
7
PBJN125 7PBJN325 7PBJN3N25
32
22.5
7
PBJN132 7PBJN332 7PBJN3N32
40
28
7
PBJN140 7PBJN340 7PBJN3N40
50
35
7
PBJN150 7PBJN350 7PBJN3N50
63
44
7
PBJN163 7PBJN363 7PBJN3N63
80
56
7
PBJN180 7PBJN380 7PBJN3N80
100
70
7
PBJN1100 7PBJN3100 7PBJN3N100
125
88
7
PBJN1125 7PBJN3125 7PBJN3N125
160
112
7
PBJN1160 7PBJN3160 7PBJN3N160
200
140
7
PBJN1200 7PBJN3200 7PBJN3N200
Switch Disconnector
7
PDJ1200 7PDJ3200 7PDJ3N200
JM FRAME MOTOR DUTY MCCBs
I
‘
JM’ Frame MCCBs have higher magnetic settings than standard ‘J’ Frame
Current
MInimum
3
Pole
Rating (A)
Setting (A)
LIST No
50
35
7
PBJN3M50
63
44
7
PBJN3M63
80
56
7
PBJN3M80
100
70
7
PBJN3M100
125
88
7
PBJN3M125
160
112
7
PBJN3M160
200
140
7
PBJN3M200
• 25
kA Icu at 415V ac
•
Fixed Magnetic elements
• 70 – 100%
adjustable thermal elements (25A-200A)
• 80 – 100%
adjustable thermal elements (16A-20A)
•
Cable clamps at both ends, 150mm
2
max
•
Switched neutral on LHS
J FRAME MCCB ACCESSORIES ELECTRICAL
I
Shunt Trip Assembly (Inc. Aux Sw)*
LIST No
18-30
V ac: 12-36 V dc
7
PAJT030
110-120
V ac:
7
PAJT110
220-240
V ac:
7
PAJT240
380-415
V ac:
7
PAJT415
Under Voltage Release (Inc. Power Pack)*
110-120
V ac (Inc. transformer)
7
PAJU110
220-240
V ac
7
PAJU240
380-440
V ac (Inc. transformer)
7
PAJU440
Auxilliary Contacts (Changeover)
1-
N/O 1-N/C
7
PAJA1
2-
N/O 2-N/C
7
PAJA2
*
Shunt trip or UVR can be fitted - not both
J FRAME MCCB ACCESSORIES GENERAL
I
LIST No
Terminal Shroud 1 Pole
7
PAJS1
Terminal Shroud 3 Pole
7
PAJS3
Terminal Shroud 4 Pole
7
PAJS4
Interphase Barrier (2)
7
PAJIB
Cable Clamps-Set of 3
7
PAJCC
Cable Extension Set (to accomodate 185/240mm
cable sockets)
7
PAJEC
Neutral Link Assembly
7
PAJN
Dolly Locking Device
7
PAJDLD
Padlock for above
7
PAFJP
Door Interlock Rotary Handle
7
PAJHR
POWERSTAR
J F RAME MCCB s
161
1
P
3
P
4
P
7
PAJHR
7
PAJEC
7
PAJIB
7
PAJDLD
7
PAJS3
‘
J’ MCCBs used with System Powerstar
Form 2:
• 1
P and 3P MCCBs only
•
Terminal Shrouds if required, outgoing side only
Form 4:
• 3
P and 4P MCCBs only
•
Door Interlock handle must be ordered for each MCCB used
•
Terminal Shrouds, if required outgoing side only