Background Image
Table of Contents Table of Contents
Previous Page  17 / 36 Next Page
Information
Show Menu
Previous Page 17 / 36 Next Page
Page Background

17

FEATURES

• Cost effective solution for new

and existing installatiions

• Web access to SNP and ‘Bus-du-

jour’® networks and controllers

– NCP, ARCNET

and LON

• Accessible from anywhere at any

time through a web browser

• Rich, dynamic graphics

• Remote monitoring and

management of alarms, events,

and trend logs

• Comprehensive security features

• Remote configuration capability

• VisiSat tunneling support

• No extra or specialist software

required

Satchwell MicroNet

TAC XENTA embedded web servers

The TAC Xenta 555 and 731 are multi-functional presentation systems with a built-in

(embedded) web server. They offer MicroNet and Satchnet users a feature rich web

solution by providing secure access to MicroNet and Satchnet networks via a web

browser. All functions are easy to use and accessible via intranets and the Internet

– around the clock, anywhere in the world.

As autonomous user interfaces, the Xenta 555 and 731 offer broader functionality

than any other product of their kind – including complete remote configuration, trend

logging, time scheduling, alarm and event monitoring. Site information is displayed

dynamically through powerful web graphics pages, with continuous updating of live

values in real time.

The Xenta 555 / 731 can also act as portals to TAC’s powerful Vista BMS, offering

a comprehensive and integrated solution for building management and security.

The Xenta 731 provides in addition a direct control capability and enhanced

network support.

Satchwell Product Catalogue – SATCHWELL MICRONET –

MicroNet 50 Series Controllers

Other supported products

MNN-30-100

MNN-44-100

MNN-50-100

MNN-62-100

MNN-LCD-100

MNN-LCDP-100

MNN-TS-100

MNN-TSP-100

MNN-MI-100

MNA-R10

MNL-TSP-100

IAC 400/420/600

IAC Touch Screen

MIU IV

UniFact

UniFact Pro

MMC 3601/4601

COMPATIBILITY

• VisiSat v.2.1 or later

• TAC XBuilder v.5.0.2 or later

• TAC Vista v.5.0.2 or later

WEB INTERFACE

Optimised for Microsoft Internet Explorer

Version 6.0 or later

Part Number

Supported Network Protocols

TAC Xenta 555

0-073-0825 LON, ARCNET, NCP, SNP

TAC Xenta 731

0-073-0165

LON, ARCNET, NCP, SNP,

I/Net, Modbus

Terminal Part TAC Xenta 400

0-073-0902

TAC Xenta:

Programming Serial Kit

0-073-0920

Data Sheet Xenta 555: 03-00044-01-en

Data Sheet Xenta 731: 03-00046-01-en

INSTALLATION DETAILS

Supply voltage:

24 V AC ±20%, 50/60 Hz or 19–40 V DC

Power consumption:

max. 5 W

Transformer sizing:

5 VA

Power Failure Protection:

Settings, e.g. configuration and web pages, are stored