17
FEATURES
• Cost effective solution for new
and existing installatiions
• Web access to SNP and ‘Bus-du-
jour’® networks and controllers
– NCP, ARCNET
and LON
• Accessible from anywhere at any
time through a web browser
• Rich, dynamic graphics
• Remote monitoring and
management of alarms, events,
and trend logs
• Comprehensive security features
• Remote configuration capability
• VisiSat tunneling support
• No extra or specialist software
required
Satchwell MicroNet
TAC XENTA embedded web servers
The TAC Xenta 555 and 731 are multi-functional presentation systems with a built-in
(embedded) web server. They offer MicroNet and Satchnet users a feature rich web
solution by providing secure access to MicroNet and Satchnet networks via a web
browser. All functions are easy to use and accessible via intranets and the Internet
– around the clock, anywhere in the world.
As autonomous user interfaces, the Xenta 555 and 731 offer broader functionality
than any other product of their kind – including complete remote configuration, trend
logging, time scheduling, alarm and event monitoring. Site information is displayed
dynamically through powerful web graphics pages, with continuous updating of live
values in real time.
The Xenta 555 / 731 can also act as portals to TAC’s powerful Vista BMS, offering
a comprehensive and integrated solution for building management and security.
The Xenta 731 provides in addition a direct control capability and enhanced
network support.
Satchwell Product Catalogue – SATCHWELL MICRONET –
MicroNet 50 Series Controllers
Other supported products
MNN-30-100
MNN-44-100
MNN-50-100
MNN-62-100
MNN-LCD-100
MNN-LCDP-100
MNN-TS-100
MNN-TSP-100
MNN-MI-100
MNA-R10
MNL-TSP-100
IAC 400/420/600
IAC Touch Screen
MIU IV
UniFact
UniFact Pro
MMC 3601/4601
COMPATIBILITY
• VisiSat v.2.1 or later
• TAC XBuilder v.5.0.2 or later
• TAC Vista v.5.0.2 or later
WEB INTERFACE
Optimised for Microsoft Internet Explorer
Version 6.0 or later
Part Number
Supported Network Protocols
TAC Xenta 555
0-073-0825 LON, ARCNET, NCP, SNP
TAC Xenta 731
0-073-0165
LON, ARCNET, NCP, SNP,
I/Net, Modbus
Terminal Part TAC Xenta 400
0-073-0902
TAC Xenta:
Programming Serial Kit
0-073-0920
Data Sheet Xenta 555: 03-00044-01-en
Data Sheet Xenta 731: 03-00046-01-en
INSTALLATION DETAILS
Supply voltage:
24 V AC ±20%, 50/60 Hz or 19–40 V DC
Power consumption:
max. 5 W
Transformer sizing:
5 VA
Power Failure Protection:
Settings, e.g. configuration and web pages, are stored
in the non-volatile (flash) memory and will not be lost after a power failure.