Background Image
Table of Contents Table of Contents
Previous Page  273 / 425 Next Page
Information
Show Menu
Previous Page 273 / 425 Next Page
Page Background

Full range of product

and technical information

place this part number

in a search engine and

download

1SCC301001C0201

4

4/59 switchgear

ABB Low Voltage Industrial Products 0312

Switch fuses accessories

Auxilliary contacts

Auxiliary contacts for OS32G ... 1250

Mounting on the left side of the switch: Max. 8 auxiliary contact blocks with the OEA28 module.

Mounting under the mechanism cover: - OS200...250: Max 4 test contacts or 2 test contacts + 2 test indication contacts.

- OS315...400: Max 4 test contacts and 4 test indication contacts. The test contacts can be used as standard auxiliary

contacts as well. Auxiliary contacts for 3 + N types only with the OEA28 module.

Product Hierarchy 2100004

Description

Order Code

Price

Module for auxiliary contacts screw mounting to the left side of the switch

OEA28

10.20

1 NO contact block

OA1G10

5.89

1 NC contact block

OA3G01

5.89

OA_G_

OEA28

S00261A

S01641A

Auxiliary contacts for OS32G ... 1250

The “test” contacts operate in ON- and OFF-positions as well as when the handle is turned to TEST

position = 45 degrees over the OFF-position. The “test indication” contacts operate only when the handle

is turned to TEST-position. See the function table below. The OA1G10 (N.O.) or OA3G01 (N.C.) auxiliary

contact blocks can be used as standard auxiliary contacts, “test” or “test indication” contacts. The

desired functions are achieved when an auxiliary contact block is installed in a specific place shown in

the mounting instruction. In order to activate the “test” and “test indication” features a handle with test

function is required.

Function table of OS32G…1250 auxiliary contacts

Handle position

Main contacts

Aux./Test contacts N.O.

Test indication contacts

N.O.

Test

open

closed

closed

0

open

open

open

I

closed

closed

open

Maximum number of contact blocks, “Aux./test” contacts and “test indication” contacts, see the table

below. Standard versions include all except for N3-types which are equipped with integrated neutral

through the mechanism.

Maximum number of auxiliary contacts under the mechanism cover

Pole version

Standard

N3

Standard

N3

Standard

N3

Maximum number of contact blocks

4

0

8

4

12

8

Aux./Test contacts

4

0

4

2

8

1)

6

2)

Test indication contacts

2

0

4

2

4

2

OS 30...60

OS 100...200