Background Image
Table of Contents Table of Contents
Previous Page  11 / 425 Next Page
Information
Show Menu
Previous Page 11 / 425 Next Page
Page Background

1/5 control gear

ABB Low Voltage Industrial Products 0312

1

A unique contactor for AC or DC control supply

– Manages large control voltage variations

– Includes an electronic coil interface with extended operating

limits 0.85 x

U

c

min. ... 1.1 x

U

c

max.

Reduced panel energy consumption

– With low holding AC and DC coil consumption

– From 30% (AF coil) to 80% (AF..Z coil) reduction of AC

pull-in consumption

Built-in surge protection

– No extra surge suppressor required

Improve your equipment reliability with AF..Z contactors

– Withstands control voltage short dips

– Withstands control voltage sags according to

SEMI F47-0706 standards

– Additional AF..Z coils available for control voltages

between 12...20 V DC and 48...250 V 50/60 Hz - DC

Only four coils for easier selection

Control voltages covering 24...500 V 50/60 Hz and

20...500 V DC

21 24...60 V 50/60 Hz / 20...60 V DC

12 48...130 V 50/60 Hz - DC

13 100...250 V 50/60 Hz - DC

14 250...500 V 50/60 Hz - DC

Direct control by PLC-output 500 mA, 24 V DC

Types

AF09 AF12 AF16 AF26 AF30 AF38

Rated operational power

400 V AC-3

4 kW 5.5 kW 7.5 kW 11 kW 15 kW 18.5 kW

Rated operational current

AC-1 (40 °C)

25 A 28 A 30 A 45 A 50 A 50 A

UL 3-phase motor power

480 V

5 hp 7.5 hp 10 hp 15 hp 20 hp 20 hp

AF09 ... AF38 3-pole contactors

Simple design with 2 frame sizes in 45 mm width

Auxiliary contacts

N.O. / N.C.

Contactor type

Main contacts

N.O. / N.C.

Blank: standard coil consumption

Z: low coil consumption

Coil code

AF09 Z - 30 - 10 - 21

No use of interface relay

Conventional

operating limits

for coil 220...230 V 50 Hz

0.85 x

U

c

min.

(85 V)

U

c

min.

(100 V)

1.1 x

U

c

max.

(275 V)

1.1 x

U

c

(253 V)

0.85 x

U

c

(187 V)

U

c

= 220...230 V

50 Hz

U

c

max.

(250 V)

U

c

min. ...

U

c

max. =

100...250 V

50/60 Hz - DC

AF operating limits

for coil 100...250 V 50/60 Hz - DC

AC

AC / DC