Background Image
Table of Contents Table of Contents
Previous Page  60 / 267 Next Page
Information
Show Menu
Previous Page 60 / 267 Next Page
Page Background

3VT2 Molded Case Circuit Breakers up to 250 A

Circuit breakers · Switch disconnectors

3/4

Siemens LV 36 · 2008

3

Selection and ordering data

Accessories

For the description of releases, see page 3/15.

1)

Only for switching units 3VT2725-. AA36-0AA0 or 3VT2725-. AA46-0AA0

2)

Only for switching unit 3VT2725-. AA56-0AA0

Rated current

I

n

Breaking capacity

I

cu

DT Order no.

PS*

Weight

per PU

approx.

A

kA

kg

Switching units

3-pole version

250

36

B

3VT2 725-2AA36-0AA0

1 unit

7.400

250

65

B

3VT2 725-3AA36-0AA0

1 unit

7.400

4-pole version, unprotected N

250

36

B

3VT2 725-2AA46-0AA0

1 unit

7.400

250

65

B

3VT2 725-3AA46-0AA0

1 unit

7.400

4-pole version, protected N

250

36

B

3VT2 725-2AA56-0AA0

1 unit

7.400

250

65

B

3VT2 725-3AA56-0AA0

1 unit

7.400

Rated current

I

n

Current setting of the inverse- time

delayed overload releases „L“

I

r

DT Order no.

PS*

Weight

per PU

approx.

A

A

kg

ETU overcurrent releases

System protection, ETU LP, LI function

1)

with fixed overload release, fixed short-circuit release

160

160

B

3VT9 216-6AB00

1 unit

0.317

200

200

B

3VT9 220-6AB00

1 unit

0.317

250

250

B

3VT9 225-6AB00

1 unit

0.317

System protection, ETU DP, LI function

1)

with adjustable thermal overload release,

adjustable short-circuit release

100

40 ... 100

B

3VT9 210-6AC00

1 unit

0.283

160

63 ... 160

B

3VT9 216-6AC00

1 unit

0.284

250

100 ... 250

B

3VT9 225-6AC00

1 unit

0.283

System protection, ETU DPN, LIN function

2)

with adjustable thermal overload release,

adjustable short-circuit release

100

40 ... 100

B

3VT9 210-6BC00

1 unit

0.327

160

63 ... 160

B

3VT9 216-6BC00

1 unit

0.327

250

100 ... 250

B

3VT9 225-6BC00

1 unit

0.327

Motor and generator protection, ETU MP, LI function

1)

with adjustable thermal overload release,

adjustable short-circuit release

100

40 ... 100

B

3VT9 210-6AP00

1 unit

0.285

160

63 ... 160

B

3VT9 216-6AP00

1 unit

0.284

250

100 ... 250

B

3VT9 225-6AP00

1 unit

0.285

Motor and generator protection, ETU MPS, LSI function

1)

with adjustable thermal overload release,

adjustable short-circuit release

100

40 ... 100

B

3VT9 210-6AS00

1 unit

0.230

160

63 ... 160

B

3VT9 216-6AS00

1 unit

0.230

250

100 ... 250

B

3VT9 225-6AS00

1 unit

0.230

Switch disconnector module

250

Switch disconnector

1)

B

3VT9 225-6DT00

1 unit

0,219

* You can order this quantity or a multiple thereof.