3VT1 Molded Case Circuit Breakers up to 160 A

Project planning aids

2/35

Siemens LV 36 · 2008

2

Dimensional drawings

Phase barriers and terminal covers

3-pole version

Fixed-mounted version

• Front connection

- Terminals 1, 3, 5

3VT9 100-8CE30 phase barriers or 3VT9 100-8CA30 termi-

nal covers have to be used (when using 3VT9 100-4TF30

connection sets for connecting circuit breakers/switch dis-

connectors, the terminal cover is included in the connecting

set).

- Terminals 2, 4, 6

3VT9 100-8CE30 phase barriers or 3VT9 100-8CA30 termi-

nal covers have to be used if the circuit breaker/switch dis-

connector is connected to the power supply using terminals

2, 4, 6 (when using 3VT9 100-4TF30 connection sets for con-

necting circuit breaker/switch disconnector, the terminal

cover is included in the connecting set).

• Rear connection

- phase barriers and covers must be used.

H

>15

Reference Size

mm

A

50 minimum distance between the circuit breaker/switch dis-

connector and uninsulated earthed wall (applicable for

connections using insulated conductors, cables, flexibars

or with rear connection)

A1

100 minimum insulation length of bare conductors (using

3VT9 100-8CE30 phase barriers from 50 mm to max. 100

mm, or by adding additional insulation for the conductors

with barriers to obtain at least A1 value)

A2

150 minimum distance:

• between circuit breaker/switch disconnector and uninsu-

lated earthed wall (applicable for uninsulated conduc-

tors and busbars)

• between circuit breaker/switch disconnector and busbar

• between two circuit breakers/switch disconnectors situ-

ated vertically above one another

• between uninsulated connections of two circuit

breakers/switch disconnectors above one another

C, D, E, F,

G

30 minimum distance between the circuit

breaker/switch disconnector and uninsulated earthed wall

H

minimum distance between uninsulated conductors

NSO0_00012

100

TEST

OFF

ON

TEST

OFF

ON

TEST

OFF

ON

H = 30

130

B =

20

A = 50

A1 = 100

A2 = 150

B = 20

75

75

100

B = 20

E = 70 G = 40

F = 0

G = 0

1

1

1

3VT9 100-8CE30