Background Image
Table of Contents Table of Contents
Previous Page  198 / 267 Next Page
Information
Show Menu
Previous Page 198 / 267 Next Page
Page Background

3VT4 Molded Case Circuit Breakers up to 1000 A

Overcurrent releases

5/12

Siemens LV 36 · 2008

5

Overcurrent releases ETU MP-Motors

• Direct protection of motors and generators

• Possibility for protecting lines and transformers

The 3VT9 4..-6AP00 release is intended only for the 3VT4 710-

3AA..-0AA0 switching unit. The operation of the release is con-

trolled by a microprocessor. The release is equipped with a

thermal memory that can be disabled by turning a switch on the

front panel from position T

(t)

to position T

(0)

. After having dis-

abled the thermal memory, the thermal release remains active.

A practical advantage of the release are specially designed

tripping characteristics that provide for optimal exploitation of

transformers up to 1.5

I

n

. It is possible to set a total of 8 charac-

teristics on the release. From these, in mode “M” there are 4

characteristics for motor protection and another 4 characteris-

tics in mode “T

V

” for protecting transformers and lines. The

shape of each characteristic can be changed using a selector

switch.

When one or two phases fail, in the M-characteristic mode, the

switch will open with a 4 s delay (so called undercurrent

release).

Another parameter for adjusting the release is the rated current,

which is adjusted in a range of 0.4 to 1.0 of

I

n

and the short-

circuit tripping level, for which it is possible to set the delay at 0

or 50 ms. The reaching of 80% and 110% of

I

r

is indicated by

LED diodes on the front panel denoted as

I

> 80% of

I

r

and

I

>

110% of

I

r

. On the lower part of the release cover four photocells

are mounted for communicating with the 3VT9 500-6AE00 sig-

nalling unit.

Specifications for adjustable releases

Order No.

Rate

d

cur-

rent

In

Overload

protec-

tion

I

r

t

r

(7.2 x

I

r

) Restar

t

Instantaneous

short circuit pro-

tection

I

A A

S

kA

ms

0.5

125, 137 1 (TV 1)

1

1.5

144, 160 3 (TV 3)

T

(0)

2

0

2.5

172, 180 10 (TV 10)

3

4

3VT9 431-6AP00

315 200, 220 30 (TV 30)

5

5

231, 243 3 (TV 3)

4

3

250, 260 8 (TV 8)

T

(t)

2.5

50

2

275, 290 15 (TV 15)

1.5

1

305, 315 25 (TV 25)

0.5

0.8

250, 260 1 (TV 1)

1.5

2

275, 290 3 (TV 3)

T

(0)

3

4 0

305, 315 10 (TV 10)

6

8

3VT9 463-6AP00

630 345, 360 30 (TV 30)

10

10

400, 435 3 (TV 3)

8

6

455, 480 8 (TV 8)

T

(t)

4

3 50

500, 550 15 (TV 15)

2

1.5

375, 630 25 (TV 25)

0.8

1

400, 435 1 (TV 1)

1.5

2

455, 480 3 (TV 3)

T

(0)

3 4 0

4

500, 550 10 (TV 10)

6

9

3VT9 480-6AP00

800 575, 610 30 (TV 30)

12

12

630, 685 3 (TV 3)

9

6

722, 760 8 (TV 8)

T

(t)

4

3 50

800, 866 15 (TV 15)

2

1.5

909, 1000 25 (TV 25)

1

1.25

400, 435 1 (TV 1)

2

3

455, 480 3 (TV 3)

T

(0)

5

0

7

500, 550 10 (TV 10)

9

12

3VT9 410-6AP00

1000 575, 610 30 (TV 30)

14

12

630, 685 3 (TV 3)

12

9

722, 760 8 (TV 8)

7

T

(t)

5 50

800, 866 15 (TV 15)

3

2

909, 1000 25 (TV 25)

1.25