Circuit-breakers, fuses
Fuse material
2010 CA08103002Z-EN
www.eaton.com19/75
Fusematerial
Z-NH-...
Z-NH-1/
Z-NH-2/
Z-NH-2/
Electrical
Standards
IEC 60269, VDE 0636, SEV 1086
Nominal voltage
AC
V AC
500
500
500
500
DC
V DC
230
440
440
440
Rated operational current
A
10 - 160
50 - 250
100 - 400
250 - 630
Rated frequency
f
Hz
45 - 62
45 - 62
45 - 62
45 - 62
Rated breaking capacity
AC
kA
120
120
120
120
DC
kA
25
25
25
25
Max. heat dissipation
I
n
= 10 A
W
1.1
-
-
-
I
n
= 16 A
W
1.6
-
-
-
I
n
= 20 A
W
1.7
-
-
-
I
n
= 25 A
W
1.9
-
-
-
I
n
= 35 A
W
3.0
-
-
-
I
n
= 40 A
W
3.5
-
-
-
I
n
= 50 A
W
4.6
5.4
-
-
I
n
= 63 A
W
5.4
6.3
-
-
I
n
= 80 A
W
5.1
7.2
-
-
I
n
= 100 A
W
6.9
8.6
8.8
-
I
n
= 125 A
W
10.3
11.9
12.1
-
I
n
= 160 A
W
11.0
13.9
14.0
-
I
n
= 200 A
W
-
15.2
15.2
-
I
n
= 250 A
W
-
21.8
21.8
19.4
I
n
= 315 A
W
-
-
23.7
23.7
I
n
= 400 A
W
-
-
30.5
30.5
I
n
= 500 A
W
-
-
-
42.0
I
n
= 630 A
W
-
-
-
47.0
Z-SLS/B
Z-SLS/B24
Electrical
Rated operating voltage
Rated operating voltage
U
e
V AC
60 - 400
24 - 60
V DC
60 - 220
24 - 60
Utilization category
gG (gL)
gG (gL)
Test voltage
kV
5
5
Mechanical
Size
D01: 1, 2, 4, 6, 10, 13, 16 A
D02: 20, 25, 32, 35, 40, 50, 63 A
Z-D0./SE
Electrical
Standards
DIN VDE 0636, DIN 49522
Utilization category
gG (gL)
Rated voltage
AC
U
n
V
400
DC
U
n
V
220
Rated frequency
f
Hz
45 - 65
Rated insulation voltage
U
i
V
2500
Rated short-circuit switching capacity
AC
kA
50
DC
kA
8