Background Image
Table of Contents Table of Contents
Previous Page  430 / 543 Next Page
Information
Show Menu
Previous Page 430 / 543 Next Page
Page Background

18/100 IZM circuit-breakers, IN switch-disconnectors

Circuit-breaker IZM26

2010 CA08103002Z-EN

www.eaton.com

Circuit-breaker IZM26

IZM20B…08… IZM20B…10… IZM20B…12…

General

Standards

IEC/EN 60947

Ambient temperature

Storage

°C -40 - +70 (Devices with LCD display -20 - +70)

Operation (open)

°C -25 - +70 (Devices with LCD display -20 - +70)

Built-in position

Utility category

B

B

B

Protection type

IP20, IP54 with protective cover

Direction of incoming supply

Any

Main contacts

Rated operational current = Rated uninterrupted current

I

n

= I

u

A 800

1000

1250

Rated uninterrupted current at 50 °C

1)

I

u

A 800

1000

1250

Rated uninterrupted current at 60 °C

1)

I

u

A 800

1000

1100

Rated uninterrupted current at 70 °C

1)

I

u

A 800

1000

1000

Rated impulse withstand voltage

U

imp

V AC 8000

8000

8000

Rated operational voltage

U

e

V AC 690

690

690

Use in IT electrical power networks up to U = 440 V

I

IT

kA 21

21

21

Use in IT electrical power networks up to U = 690 V

I

IT

kA –

Overvoltage category/pollution degree

III/3

III/3

III/3

Rated insulation voltage

U

i

V

1000

1000

1000

Switching capacity

Rated short-circuit making capacity

Up to 440 V 50/60 Hz I

cm

kA 105

105

105

Up to 690 V 50/60 Hz I

cm

kA 105

105

105

Rated short-time withstand current 50/60 Hz

t = 1 s

I

cw

kA 50

50

50

t = 3 s

I

cw

kA –

Rated short-circuit breaking capacity I

cn

IEC/EN 60947 Operating sequence I

cu

O-t-CO

Up to 240 V 50/60 Hz

I

cu

kA 50

50

50

Up to 440 V 50/60 Hz

I

cu

kA 50

50

50

Up to 690 V 50/60 Hz

I

cu

kA 50

50

50

Up to 1100 V 50/60 Hz

I

cu

kA –

IEC/EN 60947 Operating sequence I

cs

O-t-CO-t-CO

Up to 240 V 50/60 Hz

I

cs

kA 50

50

50

Up to 440 V 50/60 Hz

I

cs

kA 50

50

50

Up to 690 V 50/60 Hz

I

cs

kA 50

50

50

Up to 1100 V 50/60 Hz

I

cs

kA –

Switching times

Total opening delay

ms

30

30

30

Closing delay

ms

35

35

35

Closing delay electrical (via closing release)

ms

40

40

40

Opening delay electrical ( via shunt release / undervoltage release)

ms

35/70

35/70

35/70

Opening delay via trip electronics (non-delayed short-circuit release)

ms

35

35

35

Durability

Mechanical, without maintenance

Operations

12500

12500

12500

Mechanical, with maintenance

Operations

20000

20000

20000

Electrical, without maintenance

Operations

10000

10000

10000

Electrical, with maintenance

Operations

10000

10000

10000

Maximum operating frequency

Operations/h

60

60

60

Heat dissipation at rated operational current I

n

3-phase symmetric loading

Fixed

W 60

95

150

Withdrawable

W 110

170

260

Weight

Fixed

3 pole

kg

43

43

43

4 pole

kg

54

54

54

Withdrawable

3 pole

kg

48

48

48

4 pole

kg

62

62

62

Empty cassette

3 pole

kg

34

34

34

4 pole

kg

38

38

38

Notes

1)

Permissible continuous current for circuit-breakers used at different temperatures within switchgear.

The expected internal temperatures can be estimated according to the applicable IEC regulations.

30˚ 30˚

30˚ 30˚

IZM…