2010 CA08103002Z-EN

www.eaton.com

18/44 IZM circuit-breakers, IN switch-disconnectors

IZM26 air circuit-breakers, Switch-disconnector IN26

IZM26aircircuit-breakers,Switch-disconnector IN26

IZM26: Robust safety

Eaton's IZM26 circuit-breakers offer

a proven and complete range of air

circuit-breakers up to 6300 A. Four

sizes enable the ideal circuit-breaker

to be selected economically for any

project. In this way, only the module

width increases with the required

rated operational current, enabling the

most compact and economical size to

be selected.

The particularly rugged circuit-break-

ers are already in use 100,000 times in

harsh industrial environments world-

wide. Large material thicknesses and

a high short-time withstand current

are its characteristic features.

Applications

The circuit-breakers can be used in

four main application areas depending

on the type of equipment to be

protected:

• System protection,

• Motor protection,

• Transformer protection,

• Generator protection.

These key applications make different

demands on the switches, which are

met with a range of trip units.

Switches with closing release

They are particularly suitable for

synchronization tasks.

Coupler switches

Beside the IZM26 circuit-breakers,

IN26 switch-disconnectors are

available. These are used, for

example, as coupler switches

between different power supplies.

Modular design

Because components are installed

from the front, retrofitting accessories

is especially quick and easy. This

allows flexible response to changing

requirements within the system.

Standard scope of delivery

as usual

• With the new IZM26, you also select

a basic device that is already fitted

with an electronic release and

horizontal terminal adapters.

• The standard mounting is on a

horizontal mounting plate or on

horizontal traverses in the switching

cabinet.

• With four-pole devices, the neutral

conductor is arranged on the left

(front view).

• The neutral conductor can be

loaded 100% like the phase

conductors.

• The circuit-breakers are provided

with a standard mechanical

reclosing lockout. After an overload

trip, the fault is usually examined

first of all. After the fault is identified

and rectified, the mechanical

reclosing lockout is reset by

pressing the red mechanical trip

indicator on the front of the circuit-

breaker.

• An “Automatic Reset” can be

ordered as an option. This enables

the circuit-breaker to be restored to

operation immediately at any time

after the spring-operated stored

energy mechanism is retensioned.

In these applications compulsory

fault analysis is intentionally

avoided.

• The number of control cable

terminals depends on the

accessories fitted.

• If a cassette is ordered without the

basic device, this is already fitted

with themaximumnumber of control

cable terminals.

• The standard consists of 2 NO

contacts and 2 NC contacts for

ON/OFF status indication.

• A coding mechanism between the

basic device and the cassette pre-

vents impermissible combinations

(“Rejection Interlock”).

Expansion of Standardequipment

supplied for IZM26

Some order types from the past can no

longer be found since the following

options are now already part of the

standard scope of delivery:

• The door escutcheon is now always

included in the scope of delivery.

With withdrawable designs this is

supplied with the cassette (with-

drawable unit).

• On withdrawable units the circuit-

breaker can be pulled out to inspect

the arc chutes. With fixed units, it is

recommended that sufficient space

is provided above the circuit-

breaker to enable inspection.

An additional cover is not required.

• All basic devices that are provided

with universal protection (with

Digitrip 520M…), now feature a

display.

• On each circuit-breaker the

integrated Digitrip electronic

release is factory fitted with a

sealable protective cover.

• If a motor operator is ordered, the

“Spring-operated stored energy

mechanism tensioned” indicator

switch is automatically provided.