Background Image
Table of Contents Table of Contents
Previous Page  358 / 543 Next Page
Information
Show Menu
Previous Page 358 / 543 Next Page
Page Background

18/28 IZM circuit-breakers, IN switch-disconnectors

IZMX16 circuit-breakers

2010 CA08103002Z-EN

www.eaton.com

IZMX16 circuit-breakers

IZMX16B…06…

IZMX16B…08…

IZMX16B…10…

General

Standards

IEC/EN 60947

IEC/EN 60947

IEC/EN 60947

Ambient temperature

Storage

°C

-40 - +70 (devices with LCD display -20 - +70)

Operation (open)

°C

-25 - +70 (devices with LCD display -20 - +70)

Mounting position

Utilization category

B

B

B

Protection type

IP20, IP54 with protective cover

Direction of incoming supply

Any

Any

Any

Main contacts

Rated operational current = Rated uninterrupted

current

I

n

= I

u

A

630

800

1000

Rated uninterrupted current at 50 °C

1)

I

u

A

599

760

950

Rated uninterrupted current at 60 °C

1)

I

u

A

567

720

900

Rated uninterrupted current at 70 °C

1)

I

u

A

504

640

800

Rated impulse withstand voltage

U

imp

V AC 8000

8000

8000

Rated operational voltage

U

e

V AC 690

690

690

Use in IT electrical power networks up to U = 440 V I

IT

kA 21

21

21

Use in IT electrical power networks up to U = 690 V I

IT

kA -

-

-

Overvoltage category/pollution degree

III/3

III/3

III/3

Rated insulation voltage

U

i

V

1000

1000

1000

Switching capacity

Rated short-circuitmaking

capacity

Up to 440 V50/60 Hz

I

cm

kA 88

88

88

Up to 690 V 50/60 Hz

I

cm

kA 88

88

88

Rated short-time withstand

current 50/60 Hz

t = 1 s

I

cw

kA 42

42

42

t = 3 s

I

cw

kA -

-

-

Rated short-circuit breaking capacity I

cn

IEC/EN 60947 Operating sequence I

cu

O-t-CO

Up to 240 V 50/60 Hz

I

cu

kA 42

42

42

Up to 440 V 50/60 Hz

I

cu

kA 42

42

42

Up to 690 V 50/60 Hz

I

cu

kA 42

42

42

Up to 1100 V 50/60 Hz

I

cu

kA -

-

-

IEC/EN60947OperatingsequenceI

cs

O-t-CO-t-CO

Up to 240 V 50/60 Hz

I

cs

kA 42

42

42

Up to 440 V 50/60 Hz

I

cs

kA 42

42

42

Up to 690 V 50/60 Hz

I

cs

kA 42

42

42

Up to 1100 V 50/60 Hz

I

cs

kA -

-

-

Switching times

Total opening delay

ms

20

20

20

Closing delay

ms

25

25

25

Closing delay electrical (via closing release)

ms

30

30

30

Opening delay electrical ( via shunt release /

undervoltage release)

ms

25/50

25/50

25/50

Opening delay via trip electronics

(non-delayed short-circuit release)

ms

25

25

25

Lifespan

Mechanical, without maintenance Operations

12500

12500

12500

Mechanical, with maintenance Operations

20000

20000

20000

Electrical, without maintenance Operations

10000

10000

10000

Electrical, with maintenance

Operations

10000

10000

10000

Maximum operating frequency

Operations/h

60

60

60

Heat dissipation at rated

operational current I

n

3-phase symmetric loading

Fixed

W 36

59

92

Withdrawable

W 50

80

125

Weight

Fixed

3 pole

kg

15

15

15

4 pole

kg

20

20

20

Withdrawable

3 pole

kg

39

39

39

4 pole

kg

47

47

47

Empty cassette

3 pole

kg

18

18

18

4 pole

kg

21

21

21

Notes

1)

Permissible continuous current for circuit-breakers used at different temperatures within a switchgear assembly.

The expected internal temperatures can be estimated according to the applicable IEC Standards.

30˚ 30˚

30˚ 30˚

IZMX16...