Background Image
Table of Contents Table of Contents
Previous Page  332 / 543 Next Page
Information
Show Menu
Previous Page 332 / 543 Next Page
Page Background

18/2 IZM circuit-breakers, IN switch-disconnectors

IZMX16 air circuit-breakers, INX16 switch-disconnectors

2010 CA08103002Z-EN

www.eaton.com

IZMX16 aircircuit-breakers, INX16 switch-disconnectors

I

cu

/I

cs

at U

e

= 440/690 V AC

Basic switching capacity (B)

Normal switching capacity (N)

High switching capacity (H)

I

cu

: Rated ultimate short-circuit breaking capacity

at rated operational voltage U

e

I

cs

: Rated service short-circuit breaking capacity

at rated operational voltage U

e

Circuit-breakers

Rated operational

current I

n

A

440 V AC

I

cu

/ I

cs

kA/kA

690 V AC

I

cu

/ I

cs

kA/kA

440 V AC

I

cu

/ I

cs

kA/kA

690 V AC

I

cu

/ I

cs

kA/kA

440 V AC

I

cu

/ I

cs

kA/kA

690 V AC

I

cu

/ I

cs

kA/kA

IZMX16

630 - 1600

42/42

42/42

50/50

42/42

65/50

42/42

I

cw

at U

e

= 440/690 V AC

Basic switching capacity (B)

Normal switching capacity (N)

High switching capacity (H)

I

cw

at t = 1 s

I

cw

: Rated short-time withstand current

Circuit-breaker,

switch-disconnector

Rated operational

current I

n

A

440/690 V AC

I

cw

kA

440/690 V AC

I

cw

kA

440/690 V AC

I

cw

kA

IZMX16

630 - 1600

42

42

42

I

c

m

at U

e

= 440/690 V AC

Basic switching capacity (B)

Normal switching capacity (N)

High switching capacity (H)

I

cm

: Rated short-circuit making capacity

(Peak value) at rated operational voltage U

e

Switch-disconnector

Rated operational

current I

n

A

440/690 V AC

I

cm

kA

440/690 V AC

I

cw

kA

440/690 V AC

I

cw

kA

INX 16

630 - 1600

88

88

88

IZMX16, INX16