Circuit-breakers, switch-disconnectors

2010 CA08103002Z-EN

www.eaton.com

17/165

Technical data

General

Standards

IEC/EN 60947 and VDE 0660

Contact protection

Finger and back-of-hand proof to DIN EN 50274/VDE 0660 Part 514

Climatic proofing

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature

Storage

°C

-25…+70

Operation

°C

-25…+70

Mechanical shock resistance (IEC/EN 60068-2-27)

g

20 (half-sinusoidal shock 20 ms)

Safe isolation according to EN 61140

Between auxiliary contacts and

main contacts

V AC 500

Between the auxiliary contacts

V AC 300

Built-in position

Direction of incoming supply

Any

Degree of protection

Device

In the area of the HMI devices: IP20 (basic degree of protection)

Enclosure

With insulating surround: IP40

With door coupling rotary handle: IP66

Terminal type

Tunnel terminal: IP10

Phase isolator and cable terminal: IP00

Rated uninterrupted current

max. 160 A

max. 300 A

max. 630 A

max. 1600 A

NZMB1 NZMC1 NZMN1 NZMB2 NZMC2 NZMN2 NZMC3 NZMN3 NZMN4 NZMH4

NZMH1

NZMH2

NZMH3

Circuit-breaker

Rated impulse withstand voltage U

imp

Main contacts

V

6000

6000

6000

8000

8000

8000

8000

8000

8000

8000

Auxiliary contacts

V

6000

6000

6000

6000

6000

6000

6000

6000

6000

6000

Rated operating voltage

U

e

V AC 440

690

690

440

690

690

690

690

690

690

V DC

1)

500

750

750

Overvoltage category/degree of pollution

III/3

III/3

III/3

III/3

III/3

III/3

III/3

III/3

III/3

III/3

Rated insulation voltage

U

i

V

690

690

690

690

690

1000

1000

1000

1000

1000

For use in IT electrical power networks

V

440

690

690

440

690

690

690

690

525

690

2)

Notes

Vertical and 90° in all directions

With residual-current release XFI:

- NZM1, N1, NZM2, N2: vertical and 90° in all directions

With plug-in adapter elements

- NZM1, N1, NZM2, N2: vertical, 90° right/left

With withdrawable unit:

- NZM3, N3: vertical, 90° left

- NZM4, N4: vertical

With remote operator:

- NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90°

in all directions

90˚

90˚

90˚

90˚

1)

Details apply for 3 pole system protection circuit-breaker with

thermomagnetic release NZMN(H)1(2)(3)-A... up to 500 A.

For rated operating voltage switching on 3 contacts the following applies:

DC correction factor for instantaneous release

response value NZM1: 1.25, NZM2: 1.35, NZM3: 1.45

Setting for I

i

at DC = setting I

i

AC/correction factor DC

Switching of one pole via two series contacts

Switching of one pole via three series contacts

2)

> 800 A = 525

NZM, PN, N, NS