Background Image
Table of Contents Table of Contents
Previous Page  240 / 543 Next Page
Information
Show Menu
Previous Page 240 / 543 Next Page
Page Background

17/144 Circuit-breakers, switch-disconnectors

Selectivity: incoming circuit-breaker, outgoing circuit-breaker

2010 CA08103002Z-EN

www.eaton.com

Engineering

Incoming circuit-breaker

Outgoing circuit-breaker

Selectivity 415 V AC

between circuit-breakers enables separate shut-down of faulty system sections.

Selectivity (discrimination) exists between incoming circuit-breaker 1 and outgoing circuit-breaker 2 if,

only

outgoing breaker 2 trips at position 2 during a short-circuit.

System sections 3 and 4 continue to operate.

Incoming circuit-breaker (S1)

NZM...1-A...

NZM...2-A...

I

cu

[kA]

25(36)(50)(100)

25(36)(50)(150)

I

n

[A]

20-40 50 63 80 100 125 160 20-40 50 63 80 100 125 160 200 250 300

Outgoing circuit-

breaker (S2)

I

n

[A]

I

cu(415V)

[kA]

Selectivity threshold

I

s

[kA] for selectivity between S2 and S1, overload and short-circuit release set to max. value

FAZ–B(C)

0.5

15

T

T T T T T T

T

T T T T T T T T T

1

15

T

T T T T T T

T

T T T T T T T T T

2

15

2

T T T T T T

3

T T T T T T T T T

3

15

1.2 2 3 3 10 T T

1.5 1.5 3 5 T T T T T T

4

15

1.2 2 3 3 8 T T

1.2 1.5 3 4 T T T T T T

6

15

1.2 2 2.5 3 5 10 10 1.2 1.5 2.5 3 T T T T T T

10

15

1.2 1.5 2 2 4 10 10 1

1.5 2.5 3 10 10 10 10 10 10

13

15

1

1.5 2 2 4 10 10 1

1.2 2 3 10 10 10 10 10 10

16

15

1

1.2 1.5 2 3 8 8

1

1.2 1.5 2.5 10 10 10 10 10 10

20

15

0.8 1.2 1.5 1.5 3 8 8

1

1.2 1.5 2.5 10 10 10 10 10 10

25

15

0.7 1.2 1.5 1.5 3 7 7

0.8 1 1.5 2 10 10 10 10 10 10

32

15

1.2 1 1.5 2 6 6

1 1.5 2 8 8 8 8 10 10

40

15

– 1 1.5 2 5 5

– 1.2 1.5 7 7 7 7 10 10

50

15

– – 1.2 1.5 4 4

– – 1.5 6 6 6 6 10 10

63

15

– – – 1.5 3 3

– – – 6 6 6 6 10 10

PKZM0-...

0.16

100

T

T T T T T T

T

T T T T T T T T T

0.25

100

T

T T T T T T

T

T T T T T T T T T

0.4

100

T

T T T T T T

T

T T T T T T T T T

0.63

100

T

T T T T T T

T

T T T T T T T T T

1

100

T

T T T T T T

T

T T T T T T T T T

1.6

100

T

T T T T T T

T

T T T T T T T T T

2.5

100

T

T T T T T T

T

T T T T T T T T T

4

100

T

T T T T T T

T

T T T T T T T T T

6.3

100

4

5 5 T T T T

2

3 4 5 T T T T T T

10

100

3

4 5 6 25 T T

1.5 2.5 4 4 T T T T T T

12

50

3

4 5 6 25 T T

1.5 2.5 4 4 T T T T T T

16

50

1.5 1.5 2 3 5 7 T

1

1.6 2 2.5 T T T T T T

20

50

0.8 1.5 1.5 2 3 5 T

0.8 1.2 1.5 2 T T T T T T

25

50

1 1.5 1.5 2.5 4 T

1 1.5 2 10 T T T T T

32

50

– 1 1 2 3.5 T

– 1 1.5 8 40 T T T T

PKZ2/ZM-...

0.6

100

T

T T T T T T

T

T T T T T T T T T

1.0

100

T

T T T T T T

T

T T T T T T T T T

1.6

100

T

T T T T T T

T

T T T T T T T T T

2.4

100

1.2 2 2.5 10 T T T

1.2 2 2.5 10 T T T T T T

4

100

1

1.5 2 2.5 2.5 4 10 1

1.5 2 2.5 2.5 10 10 10 T T

6

100

0.6 0.8 1 1.2 2 3 8

0.6 0.8 1 1.2 2 8 8 8 10 10

10

100

0.5 0.7 0.8 1 1.2 2 4

0.5 0.7 0.8 1 1.2 4 4 4 5 5

16

100

0.5 0.6 0.7 0.8 1.2 1.5 3

0.5 0.6 0.7 0.8 1.2 3 3 3 4 4

25

30

0.6 0.7 0.7 1.2 1.5 2

0.6 0.7 0.7 1.2 2 2 2 3 3

32

30

– 0.6 0.7 1.2 1.5 2

– 0.6 0.7 1.2 2 2 2 3 3

40

30

– 0.6 0.7 1 1.5 2

– 0.6 0.7 1 2 2 2 2 2

PKZM4

16

100

0.5 0.8 0.8 0.8 2 5 5

0.5 0.8 0.8 0.8 2 5 5 5 5 5

25

100

0.7 0.8 0.8 1.5 5 5

0.7 0.8 0.8 1.5 5 5 5 5 5

32

50

– 0.8 0.8 1.5 4 4

– 0.8 0.8 1.5 4 4 4 4 4

40

50

– – 0.8 1.5 3 3

– – 0.8 1.5 3 3 3 3 3

50

50

– – – 1 2.5 2.5 –

– – – 1 2.5 2.5 2.5 2.5 2.5

58

50

– – – – 2.5 2.5 –

– – – – 2.5 2.5 2.5 2.5 2.5

63

50

– – – – 2 2

– – – – 2 2 2 2 2

Notes

T: total selectivity

2

1

3 4

NZM, FAZ-B(C), PKZ