4/22
Technical
Section 9
Dimensions
Section 10
REDs 25...100 A
A type 30 mA and 300 mA
Earth leakage
protection
Automatic recloser
4
Description
REDs 25...100 A , A type
2P
4P
Indication
REDs status indication
Mechanical:
by O-l (open-closed) 2-position lever
Electrical: by 2 indicator lights on the front
panel:
left: red LED
right: green LED
Remote: by 1 built-in auxiliary contact
Auxiliary contact technical data
Voltage rating (Ue)
5...230 V AC/DC 230 V AC/30 V DC
Insulation voltage (Ui)
350 V
500 V
Current rating (ln)
Min: 0,6 mA
Min: 0,1 mA
Max: 100 mA,
cos
j
= 1
Max: 0,4 A AC/
1,5 A DC
Type
Configurable : NO or
NC or intermittent 1
Hz
NO and NC
Connection by tunnel terminal
Flexible or rigid cable: max 2.5 mm
2
Reference numbers
Type
Voltage
(V AC)
Rating
(A)
Sensitivity
Idn (mA)
Width in
mod. of 9
mm
Part numbers
REDs residual current devices
2P
230
25
30
4
18687
300
4
18688
40
30
4
18689
300
4
18690
63
30
4
18691
300
4
18692
4P
400
25
30
7
18264
1 N 3 5 7
2 N 4 6 8
300
7
18265
40
30
7
18266
300
7
18267
63
30
7
18268
300
7
18269
100
300
7
18270
Coordination table, max short-circuit current (kA rms)
2P: Multi 9 circuit-breaker, fuse / A type REDs coordination
Multi 9 circuit-breakers
Fuse
C32 K60 DT40 DT40N C60 C120 NG125 gL 63
2P REDs A type
Network
230 V
L/N
25 A
4,5
6
6
6
10
10
10
6
40 A
4,5
6
6
6
10
10
10
6
63 A
-
-
-
-
10
10
10
6
4P: Multi 9 circuit-breaker, fuse / A type REDs coordination
Multi 9 circuit-breakers
Fuse
C32 K60 DT40 DT40N C60 C120 NG125 gL 80
4P REDs A type
Network
400 V
L/N
25 A
4,5
6
6
10
10
10
10
10
40 A
4,5
6
6
10
10
10
10
10
63 A
-
-
10
10
10
10
10
100 A
-
-
-
-
-
-
-
-