Page 8 - 1173-schn-lvd-aug-09

Basic HTML Version

1/5
Isobar 4c
SP&N Type A split metered boards
for use only with C60H range
Distribution boards
Technical
Section 9
Dimensions
Section 10
Technical data
Designed, manufactured
and tested to
BS EN 60439-3
Isobar disconnection system
Busbar rating
2 row 90A
1 row 90A
Direct connected meters
with pulsed output
2 row 63A rated
1 row 40A rated
Voltage rating
230/240Vac
Optional distributed
neutral
Allowing 2 pole switching at any outgoing way using
distributed neutral kit
Ingress protection
IP31 to BS EN 60529
Cable capacity neutral
and earth bar
25mm
2
DIN rail mounting
With fully shrouded busbars
Surface or flush mounting Using flush mounting kit
5 single pole blanking plates
Colour
RAL 9001 epoxy powder coated
IP2X with covers removed
2 row unit 90 amp
Part number
Outgoing ways
Dimensions
Height
Width Depth
MGAN12S12
12 +12
494
470
127
1 row unit 90 amp
Part number
Outgoing ways
Dimensions
Height
Width Depth
MGAN4S5
4 + 5
264
370
127