Application
n
The vigi earth leakage module option disconnects the circuit breaker when an
electrical earth fault is detected
n
Used to overcome high earth fault loop impedance and associated excessive
disconnection times eg long cable runs
n
Enhanced personal and equipment protection
Technical data
Adjustable sensitivity and
time delay settings
For discrimination with other RCDs
Protection against nuisance
tripping due to transient
overvoltages etc.
To IEC255-4 and IEC801-2 - 5
Class A
Immunity to DC components of up to 6mA
Remote indication of tripping
Using optional changeover contact SDV
Rating
Sensitivity settings (A)
Up to 160A
0.03*, 0.3, 1, 3 and 10
200 - 250
0.03*, 0.3, 1, 3, and 10
400 - 630
0.3, 1, 3, 10 and 30
Time delay settings (ms)
0, 60, 150 and 310
* If the sensitivity is set to 30mA there is no time delay whatever the time delay
setting. For ordering references see previous pages.
Extension boxes
n
Provide extra cabling space when using oversized cables. Colour RAL9001
Size
To fit rating
Part number
100mm
63 - 250A
MGEX160C
200mm
63 - 250A
MGEX250C
120mm
400 - 630A
MGEX630C