Page 25 - 1173-schn-lvd-aug-09

Basic HTML Version

1/22
Technical
Section 9
Dimensions
Section 10
1
C60 Vigi modules
Instantaneous 10 to 300mA
Earth leakage
protection
Possible combinations
Vigi C60 < 25 A
Vigi C60 < 63 A
C60
y
25 A
b
b
b
b
C60
y
63 A
-
b
b
Note
: guaranteed by foolproof mechanical mounting.
Combined C60 circuit breaker + C60 Vigi module:
b
b
Non-locking installation (disassembly possible) (fig. 1)
v
v
Mounting with locking (disassembly possible but with visible trace of
v
v
disassembly as per appendix G of standard EN 61009-1) (fig. 2)
Disassembly after locking, visible trace of disassembly by breaking the lock as
v
v
per appendix G of standard EN 61009-1 (fig. 5)
Hinged captive screw shield that can be sealed with a wire, used for checking
b
b
and retightening the connection terminals if required (fig. 3-4)
Technical data
Voltage rating
2P: 127...240 V AC ±10 %
4P: 220...415 V AC ±10 %
Current rating
l
n
y
25 A and l
n
y
63 A
Operating frequency
50/60 Hz
Trip unit, Instantaneous
Fixed sensitivities for all ratings
Test button: minimum operating voltage
at 50 Hz
Vigi C60 2P 127/240 V: 105 V
Vigi C60 4P 220/415 V: 189 V
Manual control, by means of a handle
providing two reset modes for the C60
circuit breaker + C60 Vigi module
assembly
Either with a single action
Or separately
The C60 Vigi module resets before the
circuit breaker
Mechanical indication
Indication of the earth fault on the front face
by a red mechanical indicator on the C60
Vigi module operating handle
Electrical indication
By the SD indicating auxiliary switch
(supplied separately)
Operating temperature
-5 °C to +60 °C
Storage temperature
-40 °C to +70 °C
Connection by tunnel
terminals
Flexible 16 mm
2
cables or rigid 25 mm
2
cables for C60 Vigi modules with ratings
y
25 A
Flexible 25 mm
2
cables or rigid 35 mm
2
cables for C60 Vigi modules with ratings
y
40 A or
y
63 A
Weight (g)
Type
2P
4P
Vigi
y
25 A 120
180
Vigi
y
63 A 150
210
Accessories
Screw shield: prevents all contact with the C60 Vigi module output terminal
b
b
screws
Spare lock: to replace the lock, after removing a C60 Vigi module previously
b
b
secured to a C60 circuit breaker
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
C60 Vigi C60
C60 Vigi C60