6
6/2
Technical
Section 9
Dimensions
Section 10
Isobar 4 MCB pan assemblies
PS type single phase
PS type three phase
Connection
systems
PS type single phase and neutral
Application
(No neutral switching facility)
All pan assemblies incorporate the unique Isobar MCB way connection feature,
which offers the user the highest levels of safety through electrical isolation of
unused ways. The PS range of pan assemblies is designed to suit single pole
applications, where switching and protection of the neutral is unnecessary.
Each pan assembly is comprised of a flat steel base incorporating DIN rail,
incoming and outgoing busbar assembly with neutral and earth terminal bars.
They can be easily incorporated into custom built enclosure systems.
Technical data
Standards:
BS EN 60439 - 1 and 3
Busbar rating:
125A
Operating Voltage:
230/240V also suitable for 110Vac operation
Frequency:
50Hz
Incomers:
As A type distribution boards, see page 1/4
Note: All Merlin Gerin 2 pole RCDs are available for
use as incomers to PS pan assemblies
Outgoers:
SP C60H MCBs, SP C60H RCBO, C60H MCB & vigi
combination
PS KN pan assemblies
Application
(No neutral switching facility)
The PS range of three phase pan assemblies is designed to suit applications
where switching and protection of the neutral is deemed unnecessary. Each pan
assembly is fully insulated incorporating DIN rail, incoming and outgoing busbar
assembly. They can be easily and quickly incorporated into custom built enclosure
systems. PS pan assemblies are designed for use with SP and TP C60H MCB,
and are also suitable for two pole two phase equipment.
Technical data
Standards:
BS EN 60439 - 1 and 3
Busbar rating:
250A
Operating Voltage:
400/415V
Frequency:
50Hz
Incomers:
MGI1253, PS pan assemblies can utilise Multi 9, 3
or 4 pole devices as incomers - additional shroud
must be used - ref. 80011
Outgoers:
SP C60H MCB, SP C60H RCBO
TP C60H MCB
SP C60H MCB and Vigi combination
TP C60H MCB and Vigi combination
SP ways
Part number
6
MGAN6PS
9
MGAN9PS
12
MGAN12PS
15
MGAN15PS
TP ways
Front cover
Part number
black
sliders
Type TN
4
MGBN4TN
6
MGBN6TN
8
MGBN8TN
12
MGBN12TN
16
MGBN16TN
18
MGBN18TN
24
MGBN24TN
Isobar pan assemblies type TN use the same as PS, each pan is mounted on a
metal top hat section.
TP ways
Part number
4
MGBN4PS
6
MGBN6PS
8
MGBN8PS
12
MGBN12PS
16
MGBN16PS
18
MGBN18PS
24
MGBN24PS
PS pan assemblies