Page 214 - 1173-schn-lvd-aug-09

Basic HTML Version

5/75
AMP/VLT analogue ammeters
and voltmeters
Metering and
measurement
Technical
Section 9
Dimensions
Section 10
Application
The meters facilitate the real-time monitoring of current and voltage.
Technical data
Ferromagnetic device
Connection:
Tunnel terminals for 1.5 - 6mm
2
rigid cable
Pseudo-linear scale over 90°
Overall dimensions:
H = 79, W = 72, D = 66mm
Weight (g):
170
Complied with standards:
IEC 51 - IEC 414
Degree of protection:
Terminal block IP40
Terminals IP20
Installation temperature:
-25°C to +55°C
Storage temperature:
-40°C to +80°C
Reference temperature:
23°C
Effect of temperature
± 0.03%/°C
on accuracy
Overload AMP ONLY
Maximum for 5 seconds: 10 In
Permanence: 1.2 In
Consumption:
1.1VA
Accuracy class:
1.5
Type
Scale
(A or V)
Connection
with CT
Width in
18mm
ways
Part
number
Amp with direct connection
0 - 30
Direct
4
16029
AMP with connection via CT
Basic device
xxx/5
4
16030
Dials
0 - 5
(See TI range on page 5/64)
16031
0 - 50
16032
0 - 75
16033
0 - 100
16034
0 - 150
16035
0 - 200
16036
0 - 250
16037
0 - 300
16038
0 - 400
16039
0 - 500
16040
0 - 600
16041
0 - 800
16042
0 - 1000
16043
0 - 1500
16044
0 - 2000
16045
VLT
Scale
0 - 300
4
16060
0 - 500
4
16061
Load
3
4
A
Load
3
4
V
Analogue AMP
Analogue VLT