Function
THP
Monitors and regulates ambient temperature in 1 or 2 zones according to 3
operating modes:
n
Comfort: 5 °C to 30 °C while the premises are occupied
n
Reduced: 5 °C to 26 °C while the premises are unoccupied
n
Above freezing: the temperature in the premises is maintained at approximately
6 °C
Ambient temperature probe
Installed inside buildings, this probe is used to measure temperature.
Operation
THP
n
Choice of operating mode:
By local pushbutton: automatic, reduced, comfort, above freezing
By external remote contact overriding the local pushbutton
The comfort operating mode overrides the above freezing mode
n
Programming:
Minimum programming time between 2 switching operations: 1 minute
Memory:
- THP1: up to 42 switching operations
- THP2: up to 168 switching operations
Programmes over 24 hours and 7 days with:
- possible anticipation of switching
- deletion of a switching operation in order to modify or cancel a sequence
Changeover to “summer-winter” time in a single operation
Technical data
THP
Electrical data:
Consumption:
1 VA
Output contact current:
5 A under 250 V
cos
ϕ
= 1, 1 A under 250
cos
ϕ
= 0.6
Display:
By liquid crystal display: Of hour, minutes, day of
the week and of contact
status
Indicator lights:
5 light-emitting diodes for
1 zone and 10 for 2
zones displaying:
- the automatic, comfort
and reduced operating
modes (yellow),
- the above freezing
operating mode (green)
- the make position of the
output contact(s) (red)
General data:
A 6 year power reserve
A quartz time base,
Difference between tripping and activation: ± 0.2 °C
Degree of protection: IP 20.1
4 mm
2
tunnel terminals
Coming with:
A non-adjustable ambient temperature probe for the
THP1
Two non-adjustable ambient temperature probes for
the THP2 ambient temperature probe
There are three types
Non-adjustable probes
of probe:
± 3 °C adjustable probes
Tempo probes
The probe-THP link is made of 1.5 mm
2
copper cables less than 50 m long