5/42
Technical
Section 9
Dimensions
Section 10
MIN, MINs, MINp and MINt timers,
PRE switch-off warning
Selection table
Time management
5
MIN
MINs
MINp
MINt
PRE
Part numbers
15363
CCT15232
CCT15233
CCT15234
15376
Technical data
Voltage (+10 %, -15 %)
230 V AC
230 V AC
230 V AC
230 V AC
230 V AC
Frequency
50 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Adjustable time delay
1 to 7 min.
0.5 to 20 min. 0.5 to 20 min. 0.5 to 20 min. 20 to 60 s
Long time delay
1 h
1 h
Consumption
1 VA
< 6 VA
< 6 VA
< 6 VA
Switching capacity (cos
j
= 1)
6 A
6 A
6 A
6 A
Operating temperature
-10 to +50°C
-25 to +50°C -25 to +55°C
-25 to +55°C -10 to +50°C
Width (9 mm modules)
2
2
2
2
2
1 screw connection per pole for
cables up to 6 mm
2
n
n
n
n
n
Selection of the type of connection (3 or 4 wires)
Selector switch Automatic
Automatic
Automatic
Mechanical compatibility with electrical
n
n
n
distribution comb busbar
Switch-off warning function
n
n
n
Impulse relay function
n
Functions
MIN, MINs
These timers allow closing and then opening of a contact in a determined time.
MINp, MINt
This timer allows closing and then opening of a contact in a determined time,
and it also provides warning that the lighting is about to be switched off
by flickering of the lamplight. (switch-off warning). The MINt timer is the same as
MINp with an “impulse relay” additional function (see ”MINt” technical data).
PRE
This is used in association with MIN or MINs timers and only on incandescent
lighting circuits (not used on fluorescent, fluocompact lamps and very low voltage
halogen lamps). It provides warning that the lighting is about to be switched off
by reducing the brightness by 50% during the 20 to 60 s warning time.