Section 10
CT contactors auxiliaries
Control
Remote control
5
The breadth of the CT contactor range satisfies most
application cases (multi-pole, pole composition,
etc.). CT contactors can be combined with auxiliary
control, protection and indication functions.
CT + spacer + IHP
2 CT + spacer + 2 CT
Operation
CT contactors equipped with one or more normally open (NO) or normally closed
(NC) contacts are controlled by latched type electrical orders. On the front face a
red indicator light indicates voltage presence at the coil terminals (A1-A2).
Manually-operated contactors have a 4-position selector switch on their front face:
Automatic operating mode
b
b
Temporary «ON» override
b
b
Permanent «ON» override: used to lock the contactor in the ON position during
b
b
installation maintenance
Shutdown
b
b
Technical data
Power circuit
CT ratings
16 to 100 A (category AC7a)
Manually-operated CT ratings 16 to 63 A (category AC7a)
Characterisation on load types
Consult Practical Advice p. 92306
Voltage rating
250 V AC (1P and 2P), 400 V AC (3P and 4P)
Frequency
50 Hz or 60 Hz
Control circuit
Voltage
12 V AC (±10 %), 24 V AC (±10 %), 230...240 V
AC (-10 % +6 %)
Coil frequency
50 Hz or 60 Hz
Inrush and holding power
Type
Rating
Consumption
Max. power
(A)
inrush
holding
(W)
(VA)
(VA)
1P, 2P
16/25
15
3.8
1.1
3P, 4P
16/25
34
4.6
1.6
2P
40/63
34
4.6
1.6
3P, 4P
40/63
53
6.5
2.1
2P
100
53
6.5
2.1
4P
100
106
13
4.2
Operating temperature: -5°C to +60°C
b
b
Tropicalisation: treatment 2 (relative humidity: 95 % at 55°C)
b
b
Compliance with standards: EN 60947-4-1, EN 61095, IEC 1095
b
b
Approvals: NF, IMQ, VDE, GOST, CCC, CEBEC
b
b
ELSV compliance (Extra Low Safety Voltage): for 25 A 2P versions with 24 V AC
b
b
control
Connection by tunnel terminals
Cable type Control circuit Power circuit
16 and 25 A 40-63 A
100 A
Flexible
2 x 2.5 mm
2
2 x 2.5 mm
2
2 x 10 mm
2
6 to 35 mm
2
Rigid
2 x 1.5 mm
2
6 mm
2
25 mm
2
6 to 35 mm
2
Marking: contactors can be equipped with clip-on markers
b
b
Accessories
Screw shields
Designed to cover terminals to avoid contact with device screws
b
b
Allow sealing
b
b
Spacer - 27062
Required to reduce temperature rise of modular devices installed side by side
b
b
Recommended to separate electronic devices (thermostat, programmable clock,
b
b
etc.) from electromechanical devices (relays, contactors)
Derating of contactors mounted in modular enclosure if inside temperature is
> 40°C
Contactor rating 40°C
50°C
60°C
(1)
16 A
16 A
14 A
13 A
25 A
25 A
22 A
20 A
40 A
40 A
36 A
32 A
63 A
63 A
57 A
50 A
100 A
100 A
87 A
80 A
(1) Spacer compulsory between each product.
Permanent ON override