4/53
TM remote controls
For C60 and C120
Protection against
overloads and short
circuits
Technical
Section 9
Dimensions
Section 10
Tm modules allow
n
Remote control of C60/C120 circuit breakers (with or without a Vigi module) via
a latched order
n
Circuit breaker resetting after tripping, while respecting safety rules and
regulations in force
n
A disconnection selector switch placed on the front panel is used to:
Disconnect the remote control
Lock the remote controlled circuit breaker in the “open” position (7mm Ø
padlock not supplied)
n
A mechanical indicator shows the “open” or “closed”status of the Tm remote
control
n
Reclosing after a fault:
Must be carried out in manual mode, locally after search and clearance of the
fault
To enable manual and local resetting, an SD auxiliary switch (part number
26927), cabled in series in the control line of the Tm to module, prevent
automatic remote reclosing
Remote reclosing is possible provided regulations are complied with:resetting
takes place by opening the control circuit for more than 1.5s
Technical data
Control voltage (Uc):
230Vac (-15% +10%)
Frequency:
50 - 60Hz
Consumption:
Inrush: -Tm C60:28VA, -Tm
C120:35VA
Holding: 2VA
Insensitive to brownouts:
0.45s
Undervoltage behaviour:
>0.45s,mechanical opening
of poles
Reclosing 2s after power is restored
Number of cycles
Tm +C60:20 000
(O-C) at 40°C:
Tm +C120 (63A):10 000
Tm +C120 (80 - 125A): 5 000
Opening time by Tm:
0.5s
Closing time by Tm:
2s
Connection
Using tunnel terminals:
1 x 6mm
2
cable
2 x 1.5mm
2
or 2.5mm
2
cables
Weight
1 - 2P: 300g
3 - 4P: 310g
Possible
combinations
Voltage
(V)
Part
number
Width in
18mm
SP ways
C60 1 - 2P
230
18310
3.5
C120 1 - 2P
230
18312
3.5
C60 3 - 4P
230
18311
3.5
MX
MN
SD
OF
auto
230V ~
MX
MN
SD
auto
230V ~
A2
A1
MX
MN
SD
OF
auto
230V ~
MX
MN
SD
OF
auto
230V ~
A2
A1