Technical data
Common
The Vigi C120 module incorporates the residual current relay and toroid in a case.
Its earth leakage module is electro-mechanical. It functions without an auxiliary
power supply source and thus has a very wide operating range
Protected against nuisance tripping due to transient overvoltages (lightning strike,
switchgear switching on the network, etc.)
Breaking and making capacity upon short circuit is equal to the breaking capacity
of the circuit breaker
Instantaneous or Selective
s
trip units
Reinforced electromagnetic compatibility
Standard type
AC class:
Standard, 50 - 60Hz
8/20ms impulse withstand: Instantaneous:
250A peak
Selective: 3kA peak
Impulse withstand:
Instantaneous: 3kA peak
Selective: 5kA peak
Remote tripping:
Possible using an MX or MN release on circuit
breaker
Connection:
Identical to C120 circuit breakers:
Flexible cables: 1.5 - 35mm
2
Rigid cables: 1 - 50mm
2
Tightening torque: 3.5Nm
Fault indication by means of a red strip on the resetting handle
Resetting the Vigi
Either using the circuit breaker handle
module, at user’s
Independently of the circuit breaker
convenience:
Test button
On front face for local operation check
Width of C120 residual current device + Vigi module: (in number of 18mm SP ways)
2P 3P
4P
6.5
(3+3.5)
9.5
(4.5+5)
11 (6+5)
Weight (g):
325
500
580