4/47
C120H circuit breakers B, C and
D curves Ratings 10 - 125A,
breaking capacity 15kA
Protection against
overloads and short
circuits
Technical
Section 9
Dimensions
Section 10
4
Breaking capacity: BS EN 60898
Type
Voltage
(V)
Breaking
capacity Icn (A)
1, 2, 3, and 4P
230 - 400
15000
Breaking capacity: BS EN 60947-2
Type
Voltage
(V)
Breaking
capacity Icn (A)
1P
130
30000
230 - 240
15000
400 - 415
4500
(1)
2, 3 and 4P
230 - 240
30000
400 - 415
15000
440
10000
(1)
Breaking capacity for 1 pole with IT isolated neutral system (case of double fault).
Weight:
Pole
Grams
1
205
2
410
3
615
4
820
9933_Section_04.indd 47