4/42
Technical
Section 9
Dimensions
Section 10
PRC, PRI surge arresters
Load protection
4
Function
Analogue telephone line protection
: the PRC surge arrester wired in series to the
private installation input protects the telephones, the PABX, the modems
(including ADSL), etc.
Protection for 2 low-current lines without common potential or 4 lines with
common reference potential
: the PRI protects the measuring instrument and PLC
«sensor» inputs and the DC power supply inputs up to 53 V and AC power supply
inputs up to 37 V.
The input current must not exceed 300 mA.
3
L'1 L1
L'2 L2
L'1 L1
L'2 L2
4 10
3
Line L1
Cables 7-8
Line L1
Cables 5-6
Line L2
Cables 11-12
Line L2
Cables 11-12
–
–
Line L’1
Cables 1-2
–
–
Line L’2
Cables 7-8
t
Cable 3
t
Cables 3-4-9-10
IN
Ligne side
IN
Ligne side
OUT
Protected side
OUT
Protected side
PRC
PRI
Mains voltage (Un)
< 130 V AC
48 V DC
Function
Analogue telephone system
b
b
–
Telephone transmitter
b
b
–
Digital telephone system
–
b
b
Automation network
–
b
b
VLV load power supply (12…48 V)
–
b
b
xDSL compatibility
b
b
–
Technical data
PRC
PRI
Part number
16337
16339
Number of protected lines
2
2
Width in 9 mm modules
2
2
Test category
IEC/VDE
C1, C2, C3, D1, B2 C1, C2, C3, D1, B2
Maximum continuous voltage (Uc)
180 V DC, 130 V AC 53 V DC, 37 V AC
Limitation voltage (Up)
300 V
70 V
Rated discharge current (8/20) (In)
10 kA
10 kA
Maximum discharge current (8/20)
(Imax)
18 kA
10 kA
Response time
< 500 ns
y
1 ns
Nominal impulse current
100 A
70 A
Rated current (I
N
)
450 mA (up to 45°C) 300 mA (up to 45°C)
Series resistor
2.2
Ω
4.7
Ω
End-of-life information by
Loss of dialling tone Loss of transmission
Weight (g)
25
65
Operating temperature
-40°C to +85°C -40°C to +85°C
Température de stockage
-25°C to +60°C -25°C to +60°C
Protection class
at terminals IP20
IP20
on the front
panel
IP40
IP40
IK
05
05
Protection against overvoltages related to lightning
strikes.