4/36
Technical
Section 9
Dimensions
Section 10
PRD-DC surge arresters
Withdrawable surge arresters
Type 2 for direct current
Load protection
4
Catalogue numbers
Internal diagram Imax (kA)
Maximum
discharge
current
In (kA)
Nominal
discharge
current
Up (kV DC)
Protection level
Un (V CC)
Nominal
mains
voltage
Uc (V DC)
Maximum steady
state voltage
U
oc stc
(V DC)
Voltage in
open circuit
Width in
module
of 9 mm
Part
number
CM
DM
CM
DM
L+/
t
L-/
t
L+/L-
L+/
t
L-/
t
L+/L-
PRD 40r-600DC
40
15
1.6 1.6 2.8 600
600 600 840 600
6
16434
PRD 40r-1000DC
40
15
3.9 3.9 3.9 1000
600 600 1230 1000
6
16436
CM: Common Mode
DM: Differential Mode
Function
The PRD-DC direct current surge arrester is designed to protect photovoltaic panels
and the "DC" input to the inverter from overvoltages due to a lightning strike.
It should be installed in a switchboard inside the building. If the switchboard is located
outside, it must be weatherproof.
Withdrawable PRD-DC surge arresters allow damaged cartridges to be replaced
quickly. They offer remote reporting of the "cartridge must be changed" message.
Standards
Certifications
IEC 61643-1
b
b
T2
EN 61643-11 Type 2.
b
b
e
PRD 40r-600DC
PRD 40r-1000DC
Replacement cartridges
Type
Replacement cartridges for
Part
number
C 40-460
PRD 40r-1000DC
16684
C 40-340
PRD 40r-600DC
16685
C neutral-340
PRD 40r-600DC
16691
Replacement cartridges