Page 101 - 1173-schn-lvd-aug-09

Basic HTML Version

4/25
REDtest 25...40 A
A type 30 mA
Earth leakage
protection
Automatic recloser
Technical
Section 9
Dimensions
Section 10
18280
Protection of people against direct and indirect
contacts. Protection of installations against insulation
faults. Disconnection of on-load electric circuits,
already protected against overloads and short-circuits.
Automatic restart after insulation monitoring of the
downstream circuit. Periodic automatic testing of the
device without downstream circuit power supply
breaking.
Description
The REDtest,
RE
sidual current
D
evice recloser, is made up of a residual current
device, a recloser and a product automatic test function (Autotest).
A type
The REDtest
phase-to-neutral
residual current devices provide
A type
earth leakage
protection: tripping due to sinusoidal AC residual currents as well as by continuous
pulsed residual currents, whether they are applied quickly or increased slowly.
REDtest 25...40 A, A type
Common technical data
Earthing grounding systems
TT and TN-S only
Power supply
From top only
Voltage rating (Ue)
230 V AC, +10 %, -15 %
Frequency rating
50 Hz
Current rating (ln)
25, 40 A
Impulse withstand voltage (Uimp)
4 kV
Insulation voltage (Ui)
500 V
8/20 µs wave immunity level
250 A
Tropicalisation
Treatment 2 (relative humidity: 95 % at 55°C)
Operating temperature
-5°C to +40°C
Storage temperature
-20°C to +60°C
Weight (g)
370
Protection class
IP20 at terminals
Connection by tunnel terminal with
guard
25 mm
2
flexible cable or 35 mm
2
rigid cable
Mounting
On DIN rail
Residual current device
Compliance with standards
IEC 61008, EN 61008
Making and breaking capacity, rated
residual current (I
D
m=Im)
630 A
Breaking capacity in association with
protection device
6000 A (gL 63 A)
Tripping time
I
D
n :
300 ms
5I
D
n :
40 ms
Short-circuit current withstand
(I
D
c = Inc)
See coordination table of circuit-breaker or fuse with
A type REDtest
Number of cycles (O-C)
Mechanical: 1,000
Fixed sensitivity releases for all ratings Instantaneous release
Test button min operating voltage
195 V
Autotest and recloser technical data
Autotest
Automatic test
Yes, without power supply breaking
Max duration of Autotest cycle
< 5 minutes
Recloser
Max duration of a restart cycle
90 s
Number of restart operations
15/hour
Maximum number of consecutive
restart attempts (if no earth fault)
3
Min interval between 2 closings
180 s
Insulation fault presence monitoring
Yes
Restart in event of transient insulation
fault
Yes
Stopping restart cycle if insulation fault
present
Yes
Power consumed by the electronics
S = 8 VA
Indication
REDtest status indication
Mechanical:
by O-l (open-closed) 2-position lever
Electrical: by 2 indicator lights on the front panel:
left: red/yellow LED
right: green LED
Remote: by 1 built-in auxiliary contact