9/14
General
The increasing presence of electromagnetic interference in industrial environments,
together with the use of equipment susceptible to such interference requires the use
of suitably protected enclosures.
In order to suppress electromagnetic interference, S3HF enclosures, due to the type
of sheet metal and special gaskets used, fulfil two functions:
● Provision of adequate screening, with the effectiveness of a Faraday cage.
● Ability to provide effective protection of sensitive equipment by using galvanised
sheet metal chassis, and by following recommended installation procedures.
Electromagnetic interference
Electromagnetic disruptions comprises an electrical field E generated by a differing
potentials, and a magnetic field M, caused by current circulation, which combine to
form electromagnetic field.
The electromagnetic interference or "noise" is a disruptive electrical signal which
affects the useful signal and it likely to cause a malfunction.
Interference can be carried through the conductors or emitted through the environment
Main sources of electrical interference and equipment
sensitive to it
● Programmable controllers.
● Electronic circuits or boards.
● Regulators.
● Input signal cables (detectors, sensors, measurement probes).
● Analogue signal cables.
Main sources of electrical interference
Material
Frequency range
Motors
10 kHz...100 MHz
Transformers/rectifiers
10 kHz...100 MHz
Inductive load switching
50 kHz...10 MHz
Spot welders
10 kHz...50 MHz
Fluorescent lamps
100 kHz...3 MHz
Relays, contactors
10 kHz...200 MHz
Switching power sources
10 kHz...30 MHz
Computers (internal clock)
50 kHz...200 MHz
Variable speed drives
10 kHz...100 MHz
Induction furnaces
0...10 kHz
Power cables, etc.
0...10 kHz
Attenuation level of EMC fields
The waves of electrical or magnetic fields are reflected when they meet the sheet
metal of the enclosure.
The effective rate of the screening or dampening "a" of the incident wave is
measured in decibels (dB) using the following formulae:
a = 20 log
E
0
E
1
(dB) for electrical fields,
a = 20 log
H
0
H
1
(dB) for magnetic fields,
E0 and E1 are the current values of the electrical field, before entering and after
entering the enclosure respectively.
H0 and H1 are the magnetic field values.
Incident
wave
Reflected
wave
Radiated
wave
Enclosure surface
Outside
Inside
09_014_016_INF_004.indd 14