Page 695 - 0700-schn-encl-10

Basic HTML Version

8/114
selection
Selection and calculation:
The desired maximum temperature inside (Ts
max
) the enclosure is
10 ºC higher than the maximum value expected for the outside (Ti
max
).
It is possible to cool the enclosure using the filtered ventilation systems.
Data
Enclosure data
Height:
2000 mm
Width:
800 mm
Depth:
500 mm
Location:
Placed on the wall
Material:
Painted sheet-steel enclosure
Thermal power dissipated by the operational components
Pd: 950 W
Information on temperature and the environment:
Maximum desired temperature inside the enclosure
Te
max
: 25 °C
Minimum desired temperature inside the enclosure
Te
min
: 25 °C
Maximum temperature dissipated in the enclosure
Te
max
: 35 °C
Minimum temperature dissipated in the enclosure
Te
min
: 25 °C
Environment:
Low pollution and low dust level
Calculation of the required fan:
Usage formulas:
Psis =
Pd – k
S (Ts
max
– Te
max
)
Flow =
f Psis/ (Td
max
– Te
max
)
Pd: Thermal power dissipated by the operational components
S = 1.4 W (H + D) + 1.8 D H = 4.6 m
2
. According to standard IEC 890
K = Constant defined by the material used to manufacture the enclosure
K = 5.5 W/m
2
°C for a solid sheet-steel enclosure
K = 3.5 W/m
2
°C for a polyester enclosure
K = 3.7 W/m
2
°C for a stainless-steel enclosure
0 to 100 m f = 3.1
100 to 250 m f = 3.2
250 to 500 m f = 3.3
In order to make the calculation, it is necessary to know the height above sea level
of the installation location:
Height above sea level: 800 m
f = Coefficient relating to the height above sea level (value)
Our example:
Psis = 950 – 5.5
4.6
(35 – 25) = 497 W
Flow rate = 3.5
697 / (35 – 25) = 244 m
3
/h
Selection from the fan quick-selection table
1 fan with standard filter ref. NSYCVF300M230PF + 1 grille with standard
filter ref. NSYCAG223LPF + 1 thermostat ref. NSYCCOTHO enable a
flow rate of 302 m
3
/h
The minimum outside temperature is lower than the desired minimum
temperature inside the enclosure.
It is necessary to install resistance heaters:
Calculation of the useful resistance heater
Usage formula
W = k S (Ts
min
-Te
min
)
Our example:
W = 5.5 4.6 (15 – 10) = 127 W
Selection from the selection guide of the resistance heaters.
1 resistance heater ref. NSYCR150WU2C + 1 thermostat ref. NSYCCOTHC
500 to 750 m f = 3.4
750 to 1000 m f = 3.5
................
08_114_CL0_007.indd 114
29/1