1
Thermostat with NC contact
Technical features
Sensor element
Bimetal
Contact
NC, forced rupture
Contact resistance
< 10 m
Service life
> 100000 cycles
Switching capacity
250 V AC; 10 A (resistive load)
120 V AC; 15 A (resistive load)
250 V AC/120 V AC 2 A (inductive load cos = 0.6)
30 W DC
Connection
Four 2.5-mm
2
terminals
Mounting
By clip on 35-mm DIN rail
Enclosure
UL94 V0 plastic, light grey
Dimensions
60
33 43 mm
Weight
40 g
Mounting position
Indifferent
Operating
temperature
–20...+80 °C (–4...+176 °F)
Protection rating
IP 20
Hysteresis
7 °K
Temperature
setting range
0...+60 °C
● Thermostat with NC contact to control the stopping of a resistance heater when
the temperature exceeds the displayed value.
● This considerably lengthens the service life of the resistance heaters since they
are used less frequently.
● Protection rating: IP 20.
● PC plastic material, self-extinguishing according to standard UL94 V0.
● Temperature adjustment range: 0…+60 °C
● Connection: four 2.5-mm
2
terminals.
● Multiple fixing systems.
● UL certification.
Display
Max. command I.
Reference
°C
10 A 250 V
NSYCCOTHC
°F
10 A 250 V
NSYCCOTHCF