8/74
SLIM electronic control
NSYCUB1100W230S
SLIM
● Range of cooling powers from 1100 W to 2700 W.
● 3 installation options: surface, partial flush and flush.
● Versions in RAL 7035 and stainless steel.
● Electronic thermostat with control option (precision of ±1 °C). Option of installing a
display as an accessory.
● Minimal depth of 162 mm in every model.
● Internal IP 55 (enclosure side) maintains the IP of the enclosure up to IP 55.
● The unit is controlled by 3 commands:
– Thermostat value.
– Signal of an anomaly (sudden disconnection, incorrect phase installation, filter
blocked with dirt, high compressor temperature, high enclosure temperature).
– Door open switch signal.
● A minimum height of 1800 mm and width of 800 mm (door) or 600 mm (side
panel) is required to install a SLIM cooling unit in a Spacial enclosure.
General characteristics
● Desired internal temperature adjustable from +20 to +50 °C.
● Maximum ambient temperature: +55 ºC.
● All the units have, in standard version, a pressure gauge with automatic reset.
If the high pressure exceeds the safe value (in the high-pressure circuit) the
pressure gauge acts by cutting off the power supply to the compressor and the
external fan.
● External and internal air circuits separated with IP 55. The fan of the internal
circuit operates permanently, preventing the appearance of hot spots in the
installation.
● Equipped with alarm relay activated by the pressostat in the high-pressure circuit.
● Respect for the environment using environmentally friendly gas R134a (HFC).
NSYCUB1100W230S
Dimensions (mm)
Height
Width (according to installation type)
Depth
1580
460 (surface) or 495 (partial flush or flush)
162
Control type
electronic with control without display
(display optional)
Unit control
thermostat+alarm+door closed
Temperature setting range
+20…+50 ºC
Maximum outside temperature
+55 ºC
Type of zero-potential alarm
Inverter contact
Cooling gas type
R134a
IP (IEC 60529)
On the internal circuit
On the external circuit
55
34
External circuit filter
No (please consult us for aggressive environments)
Mounting model
(the correct cover needs to be ordered)
surface, partial flush or flush
Available cover versions
RAL 7035 and stainless steel
(please consult us for RAL 7032)
Certifications / marking
UL in process and CE
Modular version:
1 bloc + 1 cover
Modular version: Always order one SLIM cooling unit reference plus one cover
reference.
!
08_074_79_CU014.indd 74