Page 650 - 0700-schn-encl-10

Basic HTML Version

8/69
Electronic control
Reference
NSYCUE1400W230R
NSYCUE1800W400R
Voltage
230 V; 50/60 Hz
3 400 V; 50 Hz / 3 440 V; 60 Hz
Cooling power (50/60 Hz) according to EN 14511
L35-L35
L35-L50
1400/1500 W (4780/5121 Btu/h)
1200/1300 W (4097/4438 Btu/h)
1800/1900 W (6145/6485 Btu/h)
1400/1500 W (4780/5121 Btu/h)
Dimensions
Height
Width
Depth
415 mm
750 mm
412 mm
Intensity
Starting current
Rated current
18.1/22.2 A
4.8/5.8 A
5.3/6.3 A
1.8/2.1 A
Power consumption absorbed
L35-L35
L35-L50
900/1,100 W
1100/1300 W
1000/1200 W
1200/1400 W
Energy efficiency ratio (EER)
L35-L35
1.6/1.4
1.8/1.7
Control type
Electronic controller
Temperature setting range
+20...+50 °C
Maximum outside temperature
55 °C
Noise level
64 dB (A)
69 dB (A)
Air flow
of the internal circuit
of the external circuit
860/900 m
3
/h
860/900 m
3
/h
885/900 m
3
/h
1050/1160 m
3
/h
Type of zero-potential alarm
Inverter contact
Weight of unit
48 kg
50 kg
Cooling gas type
R134a (0.95 kg)
R134a (0.95 kg)
IP (IEC 60529)
On the internal circuit
On the external circuit
54
34
External circuit filter
Option
Assembly
On top
Thermal protection recommended
(fuse melt curve)
T8A
T3A
08_068_071_CU012.indd 69
29/1