8/58
Mechanical control
Top-mounting
Cooling units for electrical switchboards
● Respect for the environment by using environmentally friendly gas R134a (HFC).
● Automatic evaporation of condensation water.
● Cooling power from 760 W to 3100 W.
General characteristics
● The temperature setting can be adjusted from +20 to +50 ºC.
● They are equipped as standard with an automatically reset pressure gauge and a
switching thermostat which, when it detects a value greater than the safe pressure
value, stops the compressor and the external fan.
● The internal and external air circuits are independent. A protection rating of IP 54
is guaranteed between the outside and the inside of the enclosure.
● The fan of the internal circuit permanently guarantees prevention against hot
spots as well as improved thermal dissipation inside the enclosure.
● The devices are equipped with switches for reporting an alarm.
● System for automatic recovery and evaporation of condensates.
● RAL 7035 colour for the standard offer.
● Units in RAL 7032 as option, please contact us.
● Stainless-steel version and other voltages on demand.
NSYCU1050W230VR
Reference
NSYCU760W230VR
NSYCU1050W230VR
NSYCU1460W230VR
Voltage
230 V; 50/60 Hz
Cooling power (50/60 Hz) according to EN 14511
L35-L35
L35-L50
760/810 W (2594/2765 Btu/h)
610/640 W (2082/2184 Btu/h)
1050/1100 W (3584/3755 Btu/h)
840/890 W (2867/3038 Btu/h)
1460/1500 W (4983/5121 Btu/h)
1200/1200 W (4096/4096 Btu/h)
Dimensions
Height
Width
Depth
340 mm
600 mm
350 mm
400 mm
700 mm
400 mm
Intensity
Starting current
Rated current
7.7 A/8.8 A
2 A/2.3 A
10.1/11.6 A
2.7/3 A
14.1/16.2 A
3.7/4.2 A
Power consumption absorbed
L35-L35
L35-L50
380/440 W
440/500 W
500/580 W
580/660 W
730/810 W
810/930 W
Energy efficiency ratio (EER)
L35-L35
2.0/1.8
2.1/1.9
2.1/1.9
Control type
Thermostat
Temperature setting range
+20...+50 °C
Maximum outside temperature
55 °C
Noise level
67 dB
69 dB
Air flow
of the internal circuit
of the external circuit
350/385 m
3
/h
350/385 m
3
/h
400/440 m
3
/h
620/680 m
3
/h
Type of zero-potential alarm
Inverter contact
Weight of unit
33 kg
41 kg
45 kg
Cooling gas type
R134a (0.5 kg)
R134a (0.7 kg)
R134a (0.75 kg)
IP (IEC 60529)
On the internal circuit
On the external circuit
54
34
External circuit filter
Yes
Assembly
On top
Thermal protection recommended
(fuse melt curve)
T4A
T6A
08_058_059_CU007.indd 58