Page 637 - 0700-schn-encl-10

Basic HTML Version

8/56
Mechanical control
Side-mounting
Cooling units for electrical switchboards
● Respect for the environment by using environmentally friendly gas R134a.
● Cooling powers of 2500 W and 4000 W.
General characteristics
● The temperature setting can be adjusted from +20 to +50 ºC.
● They are equipped as standard with an automatically reset pressure gauge and a
switching thermostat which, when it detects a value greater than the safe pressure
value, stops the compressor and the external fan.
● The internal and external air circuits are independent. A protection rating of IP 54
is guaranteed between the outside and the inside of the enclosure.
● The fan of the internal circuit permanently guarantees prevention against hot
spots as well as improved thermal dissipation inside the enclosure.
● The devices are equipped with switches for reporting an alarm.
● Option of partial-flush mounting.
NSYCU4000W400VL, NSYCU1800W400VL
Reference
NSYCU1800W400VL
NSYCU2500W400VL
NSYCU4000W400VL
Voltage
3 440 V; 50 Hz / 3 440 V; 60 Hz 3 440 V; 50 Hz / 3 440 V; 60 Hz 3 440 V; 50 Hz / 3 440 V; 60 Hz
Cooling power
(50/60 Hz) according to EN 14511
L35-L35
L35-L50
1800/1900 W (6143/6485 Btu/h)
1400/1500 W (4779/5121 Btu/h)
2500/2600 W (8533/8876 Btu/h)
2000/2100 W (6828/7169 Btu/h)
3800/4100 W (12973/13997 Btu/h)
3100/3300 W (10583/11266 Btu/h)
Dimensions
Height
Width
Depth
1000 mm
400 mm
220 mm
1406 mm
502 mm
300 mm
1406 mm
502 mm
300 mm
Intensity
Starting current
Rated current
6.8/7.9 A
2.1/2.5 A
9.8/12.1 A
2.6/3.2 A
10.0/11.6 A
3.3/3.9 A
Power consumption absorbed
L35-L35
L35-L50
1200/1400 W
1400/1600 W
1500/1800 W
1800/2100 W
1900/2200 W
2200/2600 W
Energy efficiency ratio (EER)
L35-L35
1.5/1.4
1.7/1.4
2.0/1.9
Control type
Thermostat
Temperature setting range
+20...+50 ºC
Maximum outside temperature
55 ºC
Noise level
69 dB (A)
Air flow
of the internal circuit
of the external circuit
550/600 m
3
/h
620/680 m
3
/h
750/820 m
3
/h
1200/1310 m
3
/h
1200/1340 m
3
/h
1070/1190 m
3
/h
Alarm type
Inverter contact
Weight of unit
46 kg
75 kg
Cooling gas type
R134A (0.75 kg)
R134a
IP (IEC 60529)
On the internal circuit
On the external circuit
(protection of cooling elements)
54
34
55
34
External circuit filter
Yes
No (please consult us for
aggressive environments)
Assembly
Side
Thermal protection recommended
(fuse melt curve)
T 3A
T4 A
T6 A
08_054_057_CU006.indd 56