8/52
Mechanical control
Side-mounting
Cooling units for electrical switchboards
● Respect for the environment by using environmentally friendly gas R134a (HFC).
● Cooling power from 240 W to 4000 W.
● Option of partial-flush mounting for certain models.
General characteristics
● The temperature setting can be adjusted from +20 to +50 ºC.
● They are equipped as standard with an automatically reset pressure gauge and a
switching thermostat which, when it detects a value greater than the safe pressure
value, interrupts the compressor and the external fan.
● The internal and external air circuits are independent. A protection rating of IP 54
is guaranteed between the outside and the inside of the enclosure.
● The fan of the internal circuit permanently guarantees prevention against hot
spots as well as improved thermal dissipation inside the enclosure.
● The devices are equipped with switches for reporting an alarm.
● Cooling power from 240 W to 4000 W.
● RAL 7035 colour for the standard offer.
● Units in RAL 7032 as option, please contact us.
● Stainless-steel version and other voltages on demand.
NSYCU760W230VL
Reference
NSYCU240W230VL
NSYCU370W230VL
NSYCU760W230VL
Voltage
230 V, 50/60 Hz
Cooling power (50/60 Hz) according to EN 14511
L35-L35
L35-L50
240 W (819 Btu/h)
190 W (649 Btu/h)
370/390 W (1,263/1,331 Btu/h)
300/310 W (1,024/1,058 Btu/h)
760/810 W (2,594/2,765 Btu/h)
610/640 W (2,082/2,184 Btu/h)
Dimensions
Height
Width
Depth
450 mm
350 mm
140 mm + (15 mm internal)
620 mm
300 mm
170 mm
800 mm
350 mm
195 mm
Intensity
Starting current
Rated current
2.8 A
0.7 A
5.8/6.7 A
1.5/1.8 A
7.7/8.8 A
2.0/2.3 A
Power consumption absorbed
L35-L35
L35-L50
140 W
160 W
290/330 W
330/380 W
380/440 W
440/500W
Energy efficiency ratio (EER)
L35-L35
1.7
1.3/1.2
2.0/1.8
Control type
Thermostat
Temperature setting range
+20...+45 °C
+20...+50 °C
Maximum outside temperature
50 °C
55 °C
Noise level
58 dB (A)
65 dB (A)
67 dB (A)
Air flow
of the internal circuit
of the external circuit
160 m
3
/h
320 m
3
/h
160/175 m
3
/h
210/230 m
3
/h
350/385 m
3
/h
350/385 m
3
/h
Alarm type
Inverter contact
Weight of unit
15 kg
21 kg
33 kg
Cooling gas type
R134a (0.25 kg)
R134a (0.3 kg)
R134a (0.5 kg)
IP (IEC 60529)
On the internal circuit
On the external circuit
54
34
External circuit filter
Option
Yes
Assembly
Side
Thermal protection recommended
(fuse melt curve)
T1.6A
T3A
T3A
08_052_053_CU005.indd 52