8/36
Top-mounting model
General characteristics
● Main components: thermostatic adjustment system, exchange cassette, circulation
fans for internal and external circuits.
● The desired temperature inside the enclosure can be adjusted over a range of
+25 ...+50 ºC.
● The internal and external air circuits are completely separated (IP 54). Two fans
guarantee air circulation in each of these circuits. The one on the internal circuit
(which circulates the air inside the enclosure) is permanently on to avoid the
appearance of hot spots in the electric circuits or components.
● The devices are delivered with a cut-out template, an instruction sheet and a
sealing gasket to be placed between the exchanger and the enclosure.
● RAL 7035 grey.
● Voltages on demand with 400 V AC, three phase or single phase.
Conditions of use
● The exchangers can only be used if the outside temperature is at least 5 ºC lower
than the desired temperature inside the enclosure.
● The enclosure must be sealed to prevent the entry of external air.
NSYCEA50W230VRE
(1) The power in watts is obtained by multiplying the specific power by the difference between
inside temperature and outside temperature.
Reference
NSYCEA50W230VRE
Cooling characteristics
Specific power (1)
50 W/°K
Air flow of the external circuit
450 m
3
/h
Air flow of the internal circuit
450 m
3
/h
Exchange surface
3.3 m
2
Adjustment
Yes
Type
Thermostatic
Temperature setting range
+20...+50 °C
Nature of the fluid
Air
Electric characteristics
Input voltage
230 V - 50/60 Hz
Starting/rated current
2.1/0.7 A
Electrical energy absorbed
150 W
Physical characteristics
External dimensions A B C (mm)
390 600 365
Internal IP / external IP
IP 54/IP 22
Weight of unit
19 kg
Noise level
64 dB